_CONTACT BEDS._

The almost universal adoption at the present time of biological methods

of sewage purification by means of artificial filters, is due entirely

to the original experimental work of Mr. W. J. Dibdin, at the Barking

Outfall Works of the London County Council. These experiments were

carried out with a contact bed, and during the subsequent ten years

an enormous number of works were constructed upon this principle. At

the present time, however, it is a somewhat rare occurrence to find

contact beds proposed for sewage disposal schemes of any size. It

has been stated that the principle upon which they are operated is

unscientific, that they rapidly become clogged and useless, and that,

in any case, they are not capable of dealing with sewage at the same

rate as percolating filters, or of producing such a high degree of

purification. With regard to the first point it would be futile to

endeavour to explain what is and what is not scientific. This must be

left to the scientists. That contact beds have in many cases become

clogged and useless cannot be denied, but there is also very little

doubt that this unsatisfactory result has been due to one or more

of the following causes: (_a_) overwork, (_b_) improper methods of

operation, (_c_) the use of unsuitable material for filling the beds,

(_d_) insufficient sub-drainage. It was most unfortunate that for some

years the general idea of a contact bed was that it consisted of a

simple excavation in the ground, filled with coke or similar material,

into which the sewage was discharged, held up for two hours, and then

drawn off; a very simple but crude affair altogether. It is now known

that contact beds, like other systems, can only deal with limited

volumes of sewage, the actual amount depending upon the character

of the sewage and other factors; that there is a proper method of

operating the beds, and that it must be strictly adhered to if the best

results are to be produced; that unsatisfactory material is worse than

useless, and that very ample means of sub-drainage are absolutely

essential to the continued efficiency of the beds. It is probable that

if these essential factors had been properly understood and acted upon

from the outset, there would have been very few failures to record.

It has been stated that contact beds are obsolete, but there are

engineers who even now recommend this system, and consider it

satisfactory under some, if not under all conditions. In the opinion of

the author contact beds are not obsolete, and there are cases where the

conditions preclude the adoption of any other method of purification.

Under these circumstances, it is considered desirable to describe in

the following pages the details of design and construction which have

been found by experience to be necessary to ensure satisfactory results.

_General Principles of Design._—The first point to be decided before

commencing the design of a scheme of contact beds is whether single,

double, or triple contact is necessary to produce the desired degree of

purification, and this will depend upon the strength of the sewage and

the destination of the final effluent. Single contact alone will not be

sufficient, except in a very few cases where the sewage is weak (highly

diluted), and even then it will necessitate the use of fine-grade

material for filling the beds, and consequently a tank effluent of

exceptional quality as regards the matters in suspension in order that

the fine material may not be rapidly choked. Where a sufficient area of

land of a suitable character can be procured at a convenient level for

treating the effluent from the beds, single contact may be adopted with

material of medium-grade, but even in this case special attention must

be devoted to the preliminary process in tanks, so as to reduce the

amount of solids in suspension in the tank effluent to the minimum. As

a rule it will be found safer to adopt double contact, as the primary

beds may then be filled with coarse grade material, which will be less

liable to choke, and it will not be necessary to rely so much upon the

land or any other final process that may have been provided. In special

cases, and particularly where the sewage is strong, or an exceptionally

high degree of purification is essential, triple contact should be

adopted, but the tertiary beds may consist of a set of sand filters

similar in construction to those described on pages 185 to 188. In some

quarters the question of the grading of the material is considered of

slight importance, and very little difference has been made in the size

of the material for the primary and secondary beds, but in the author’s

opinion it is absolutely essential that each series of beds should be

filled with finer material than the preceding series, and the material

in the final stage of treatment should be as fine as possible, so long

as it does not contain any dust. In making these statements, it is

assumed that the question of sub-drainage will be dealt with on the

lines recommended later under that heading.

Another factor which has an important bearing upon the general design

of a scheme of contact beds, is the method of operation which is to

be adopted. It is generally assumed that all contact beds are worked

in what is known as eight-hour cycles: viz. 1 hour filling, 2 hours

standing full, 1 hour emptying, and 4 hours standing empty for rest and

aeration. There has, however, been a tendency in the past to overlook

the fact that the periods of standing full, and of emptying the beds,

are the only sections of the cycle which are, as a rule, under absolute

control. Unless special provision is made for the purpose, the time

taken to fill each bed depends entirely upon the rate of flow of the

sewage to the works, and the period of rest empty also depends upon the

frequency with which the beds are filled, and thus indirectly upon the

rate of flow of the sewage. For example, a set of four beds designed to

receive each three fillings per day in wet weather, should not receive

more than one filling per day in dry weather. Assuming that one-half

the total flow comes down in six hours, it will be found that it takes

six hours to fill two beds in the middle of the day, or three hours to

fill one bed. During the remaining eighteen hours the other two beds

are filled, one of them in say six hours and the other in twelve hours.

The times taken to fill the four beds in this scheme would therefore

be—No. 1, three hours; No. 2, three hours; No. 3, six hours; and No.

4, 12 hours. In each case the period of filling is thus much in excess

of the one hour prescribed under the eight hours cycle. The obvious

remedy is to subdivide the total area into a larger number of smaller

beds, but if this is carried to its logical conclusion it will be seen

that there must be 24 beds if the time taken to fill any one bed is

not to exceed one hour. While it is very desirable to arrange this

subdivision in order to secure the proper cycle of operations, the

number of schemes where it is economically practicable are few, and

recourse must be had to some other method of reaching the same end.

This has already been recognised by most engineers, and provision is

now usually made for a tank known under various names, such as dosing

tank, collecting tank, equalising tank or holding-up tank, in which the

tank effluent is stored until the volume accumulated is equal to the

capacity of one contact bed, and the latter is then filled within the

regulation time of one hour. If the necessity for making provision on

these lines to ensure the proper working cycle had been recognised in

the early days of contact beds, it would doubtless have prevented the

troubles which have arisen in many places.

From the preceding observations, it will be seen that it is very

necessary to come to a decision as to the method of operation to be

adopted, before designing any scheme of contact beds. If the method

of subdivision into a large number of small beds is preferred,

the planning of the separate series, and the probable cost of the

additional work involved, must be taken into consideration. On the

other hand, if a smaller number of larger beds with a suitable dosing

tank are preferred, the extra fall required for the latter must be

provided for, even if it involves the reduction of the depth which

would otherwise be available for the beds themselves.

[Illustration: FIG. 136.]

There is still another matter which has a considerable influence upon

the general design of a scheme of contact beds, viz. the slope of the

ground upon which they are to be constructed. If it has a fairly rapid

and even slope, the tanks and beds may be arranged close together, as

shown in Fig. 136. The only part that needs special care in this case

is the cross-wall between the primary and secondary beds, which will

need strengthening, especially in its lower half, in order to resist

the extra pressure it is required to take.

[Illustration: FIG. 137.]

Where the slope is not so great, a saving in the cost of excavation may

be effected by arranging the separate tiers of beds at some distance

apart, as indicated in Fig. 137, and connecting one with the other

by pipes. The aim to be attained in arranging the beds under these

conditions is to have the entire area of the floors on solid soil, with

the walls half in and half out of the ground.

Another set of conditions occasionally met with, is where the site of

the works is perfectly flat and the position of the outlet for the

final effluent involves the construction of the secondary beds either

wholly or partly below the surface. In such cases the primary beds will

come above ground, and it will then be found economical to arrange each

set of beds in two rows end to end, with a central combined supply

channel and effluent carrier, the latter being formed in the space

between the walls which support the former, as shown, Fig. 138. If

there is not sufficient head to allow of the supply channel being made

deep enough to serve as the dosing tank, the latter may be constructed

across the ends of the settling tanks, as suggested in Fig. 139, or in

any other convenient position. A dosing tank in this position lends

itself to the method of feeding the beds by means of closed pipes

instead of by open channels, whether in sets of four, with a central

chamber for the inlets and outlets illustrated in Fig. 139, or in

series as Figs. 136 and 137.

[Illustration: FIG. 138.]

There are doubtless other alternatives, or combinations of methods,

which may be adapted to meet the exigencies of peculiar conditions

of site and fall, but the foregoing details will probably suffice to

suggest ideas to those in need of them in designing schemes of contact

beds.

_General Construction._—The most important point to be borne in

mind in constructing contact beds is, that they must be absolutely

watertight. Should they leak in any way, the sewage may pass away

untreated; or it may find its way into adjacent beds, and thus prevent

these from being properly aerated during the periods of rest when

empty. It is therefore evident that they should be constructed in

a substantial manner. The floors are usually of concrete, and the

thickness of the floor will depend upon the nature of the subsoil.

If for any reason the floors have to be laid upon made-up ground,

provision should be made by means of piers or cross-walls, carried down

to the solid subsoil to support the floor, independent of the made-up

ground which is, in all cases, absolutely untrustworthy. The walls

of the beds may be constructed either of concrete throughout or of

brickwork in cement, and they should be of such a thickness that they

will withstand the pressure of the head of water which would result if

the beds were filled to the top of the walls.

It will not be found satisfactory to place reliance either upon

brickwork or upon concrete alone to form a watertight bed, and in both

cases the whole of the floors, as well as the walls, should be rendered

with cement mortar in the proportion of 2 parts of sharp clean sand to

1 part of Portland cement. No rendering should be done during frosty

weather or during excessive heat, as in both cases it will

usually be found defective, and it is better to stop the work

altogether for a time than have to patch it up afterwards.

[Illustration: FIG. 139.]

One safeguard which can be adopted to prevent difficulties later on,

is to insist upon testing all such beds with water to the full height

before any of the filtering material is placed in position. Any slight

defects which may appear can be made good then at very little expense.

If the defects are not discovered until after the beds are filled with

the filtering material, they can only be properly rectified by removing

the material, and this involves a considerable outlay. In order that

these tests may be carried out without friction, it is necessary to

stipulate clearly in the specification for the work that each bed is to

be tested with water to the full depth before any material is placed

in the bed, and that the contractor must take full responsibility for

making the beds absolutely watertight. It is, of course, understood

that the method of construction adopted by the engineer is such that,

if properly executed, the beds will be absolutely watertight; and,

in order to prevent any misunderstanding, an item should be included

in the quantities for the contractor to provide whatever sum he may

consider necessary to allow for making these tests. It may be thought

sufficient to state simply that the contractor should make all

absolutely watertight, and to leave it to him to provide the means for

doing so. It will, however, be found more satisfactory to all concerned

to provide all means both in specification and in the quantities for

attaining the desired results. It is not sufficient even to use the

word “watertight” alone in this connection, as the interpretation of

this word may be subject to differences of opinion which are obviated

by the addition of the word “absolutely.”

The foregoing observations refer not only to contact beds but to the

tanks and other portions of the work which are required to hold water.

_Methods of Distribution._—Much diversity of opinion exists with

reference to the question of distribution in filling contact beds. The

many methods which have been tried in various places, may be arranged

under four headings, viz. (_a_) above the surface of the material;

(_b_) at the surface level; (_c_) just below the surface; (_d_) at the

bottom of the bed. Some engineers hold the opinion that distribution

over a large area of the material has no value, and that it matters

little how the bed is filled so long as the liquid finds its way into

the interstices of the material with as little disturbance as possible.

The simplest method which fulfils these requirements is to allow the

sewage to flow over the surface at the inlet end of the bed, but this

soon causes the surface at this point to become clogged, and unless

it is cleaned at frequent intervals the solids very quickly become

washed down into the bed, and in the end this portion of the material

will have to be removed and washed before it can be used again. The

efforts to avoid this trouble have resulted in the numerous methods of

distribution referred, to above.

Taking them in the order given, the idea of discharging the sewage

above the surface level (_a_) by means of elevated troughs or pipes,

has been to imitate to some extent the method found necessary in the

case of percolating filters, and thus aerate the sewage before it

enters the bed. The difficulties which arise in this case are that some

extra fall is needed, and the provision of the troughs or pipes with

suitable supports is costly. It is also extremely difficult to arrange

the distribution by these means so that it shall be uniform over the

whole area, and unless this is done it cannot be of much advantage.

Distribution at the surface level (_b_) may be provided by means

of shallow grips in the material itself, and these have the great

advantage that if they become clogged to such an extent as to prevent

the sewage from freely passing into the bed, it is a small matter for

the manager to cut a fresh grip in another direction and leave the

first one to dry up when the sludge in it can be easily removed by

hand. Another method is to use rows of stoneware channels, or wooden

or iron troughs, with their edges set level with the surface of the

material, so that the sewage may flow over the edges or through holes

or notches in the sides. This is usually satisfactory, but it is not

an easy matter to maintain all the channels at the same level, and

after they have been in operation for a time it will be found that the

material immediately under the troughs or channels is badly clogged,

and can only be cleaned or renewed by removing the channels.

Sub-surface distribution (_c_) is arranged by means of perforated or

open-jointed pipes, laid below the surface of the material and thus

out of sight. The reasons for adopting this method are: that it avoids

the unsightliness caused by surface distribution; that the surface is

kept free from obstructions, and thus allows free aeration when the bed

is emptied; and last, but not least, it prevents any nuisance arising

from the evolution of obnoxious gases in the tank effluent whenever

it is over-septicised, a not infrequent occurrence in the case of

old-fashioned schemes, or in new works where the volume of sewage for

which the tanks were designed has not yet reached its maximum. This

method has the disadvantage that when the openings in and between the

pipes become choked, more labour is involved in cleaning them than in

the case of open channels or troughs on the surface.

Filling from the bottom (_d_) is assumed to possess all the advantages

and none of the disadvantages caused by the other methods. The

distribution is certainly uniform, as the liquid first fills the

sub-drains and then rises at the same level throughout the whole of the

material, forcing out any carbonic acid gas that may have accumulated

in the lower part of the bed. As the sewage does not appear on the

surface at all, there is no unsightliness and no trouble from bad

odours. On the other hand, it is evident that the solids in suspension

in the sewage or tank effluent are retained at the bottom of the bed,

especially in the under-drains, and thus they will appear in large

quantities in the effluent. Unless some special provision is made, by

means of an effluent settling tank or sand-filter, to arrest these

solids in suspension in the final effluent, they will be liable to

cause trouble in the stream, and will, in any case, seriously affect

the results of any analyses that may be made. The usual manner of

arranging this method of filling, is to cause the sewage to flow into

an open or covered chamber at the inlet to the bed, the walls of the

chamber being provided at the floor level with openings connected to

the sub-drains laid on the floor of the bed.

Whatever method of distribution is adopted, it is desirable that the

surface of the filter material shall be not less than 3 inches above

the highest level to which the sewage will rise, so that the liquid may

not be visible at the surface.

_Sub-Drainage._—Reference has already been made to the fact that

lack of ample under-drains has often been the cause of the failure

of contact beds in the past. The general practice for a long time

consisted in placing a layer of coarse material on the floor of the

bed, and providing a few rows of ordinary agricultural drain-pipes laid

with open joints. In some few cases special perforated pipes were used,

in others the pipes were partly embedded in the concrete floor. In the

opinion of the author, however, no drains in the form of pipes are

satisfactory, as they do not leave a space _at_ the floor level as a

free exit for the solids in the effluent. Where pipes are used it will

generally be found after a few months’ operation that these solids, in

the form of black sludge, have accumulated along the sides of the pipes

and among the material at the floor level, and when this once commences

the accumulation continues to take place, rising gradually in the bed

until the interstices are choked to such an extent that the liquid

capacity of the bed is reduced to a fraction only of its original

volume. The trouble was intensified by the comparatively small number

of the pipe drains usually found in the beds. It was evidently assumed

that the matters would travel laterally through the layer of coarse

material at the floor level. Unfortunately an additional impediment to

the free flow of these matters was caused in many cases by the want of

sufficient fall on the floor itself. Very little consideration will

show that a large area of floor requires a considerable slope in order

to produce the velocity of discharge necessary to remove matters in

suspension, yet it was seldom that a gradient of more than 1 in 200 was

provided, and in a few cases the surface of the floor was absolutely

flat. Under these conditions it is difficult to see how any other

result could be expected. It may be argued that it was not properly

understood in those days that the solids in suspension (converted

organic matters, the products of oxidation) must be removed if the

filtering material is to retain its working capacity, but this fact has

long been recognised in connection with percolating filters, which have

in most cases been constructed upon complete false floors, provided

with perforations, and with a suitable slope on the surface of the

actual floor.

There is very little doubt that the question of providing ample means

of sub-drainage deserves special consideration; and, in the author’s

opinion, the floors of all contact beds should be laid with much

greater fall to the outlet than in the past, and they should, in

addition, be covered entirely with a false floor of special floor-tiles

of the kind described in connection with percolating filters (pages 91

to 94). If the usual bottom layer of coarse material is then laid upon

the false floor, it will be found that the beds will maintain their

normal working capacity for a much greater length of time than in beds

constructed on the old style. Instead of arranging the slope on the

floor from the inlet end to the outlet end of the bed, it is preferable

to construct an effluent channel with a suitable fall down the centre

of the bed to the outlet, and arrange the floor with a cross-fall from

the sides to the centre channel, which may be covered by slabs of

concrete or stone laid upon the top of the floor tiles where they abut

upon the edges of the channel as suggested, Fig. 139_a_.

[Illustration: FIG. 139_a_.]

_Material for Filling Contact Beds._—The remarks made under the

heading “Filtering Material” for percolating filters (pages 101 to

103), apply with equal force to contact beds. In none of the many

cases which have come under the observation of the author has it been

possible to obtain such satisfactory results from other material as

from clinker, when used under the same conditions as to the strength

and volume of the sewage treated. It is true that excellent effluents

have been produced by beds filled with burnt clay, broken bricks or

stones, but it will usually be found that in such cases the material

is more or less clogged, and that the volume successfully treated

per day is considerably less than that which would be dealt with by

clinker. The reasons are the same as those already mentioned in pages

101 to 103, and there is no need to say more here than to recommend as

strongly as possible the use of hard-burnt vitrified furnace clinker as

already described for percolating filters.

The foregoing remarks apply more particularly to the material for

coarse and medium-grain contact beds. Clinker of the kind described is

equally suitable for fine-grain contact beds, but it is difficult to

break it to the required grade except at great cost, and a considerable

loss in bulk due to the production of fine dust. For fine-grain beds,

requiring material specified to pass a ¼-inch square mesh,

and to be retained on a ⅛-inch square mesh, clean coke-breeze from

gas-works (not ashes) will be found to be the most efficient. The

important point to be observed in preparing material for fine-grain

contact beds is that, while none of the particles should exceed

¼ inch in diameter, as many as possible of the finer particles,

⅛ inch and 3/16 inch in diameter, should be retained, but all dust

should be removed even if it necessitates washing the material for that

purpose. Even the finer particles down to 1/16 inch diameter might be

used, but it will be found extremely difficult to arrange the sifting

process to arrest these without retaining the dust as well, especially

if the material is at all damp, as the fine meshes required for the

purpose quickly become clogged with the dust, and the sieve or screen

is rendered useless.

Among other materials which may be adopted for fine-grain contact beds,

broken saggars in the pottery districts, or slag in the neighbourhood

of ironworks, are probably the next best, but only if they are properly

graded in the manner described above. Indeed the chief difficulty in

securing this fine-grade material is the preparation and grading,

particularly where large quantities are required and the situation

of the beds involves much handling of the material after it has been

sifted. It is, however, of such extreme importance to have it as fine

as possible, without including any dust, that the stipulations in the

specification with regard to this material should be made very clear

and definite, so that the contractor may make sufficient provision

in his prices to enable him to comply with the specification in its

strictest sense.

In addition to the bottom layer of floor-tiles and coarse material

prescribed in the section relating to sub-drainage, it will be

necessary to provide an additional layer above this, about 3 inches in

depth, of a medium grade, to support the very fine material and prevent

it being washed through the interstices in the coarse bottom layer, and

special attention must be devoted to the method of distribution at the

surface in order to avoid disturbance of the fine material.

[Illustration: FIG. 140.—AUTOMATIC APPARATUS FOR CONTACT BEDS.]

_Automatic Apparatus for Contact Beds._—Although contact beds can be

operated by hand, this involves continuous and regular supervision by

a man, and, unless he is under strict control, the proper cycle of

operation may not be adhered to, and the result will, in that case,

not be satisfactory. In the early days of contact beds, several types

of apparatus were designed for the purpose of operating these beds

automatically, so that the cost of manual labour would be reduced to

a great extent, and in addition, the possibility of mismanagement

avoided. Among these appliances, one of the most widely known is that

manufactured by Messrs. Adams Hydraulics, Limited; and shown in Fig.

140. In small installations, the low draught syphons described above in

connection with dosing apparatus are used to give alternate fillings

to pairs of contact beds. Where more than two beds are in use the

automatic air-lock feed is used. This consists of a cast-iron inverted

U-pipe, both legs of which are trapped, either in self-contained

castings or in separate chambers. The sewage flows through one, the

others being charged with air. When the sewage in the bed has reached

the proper height it overflows into a small chamber in which a dome is

fixed. This dome is connected by means of an air-pipe to the cast-iron

inlet feed, and as the sewage rises in the chamber round the dome, the

air contained therein is forced up into the feed which it fills, thus

forming an air-lock, which prevents the sewage from passing through and

stops the supply to the bed. At the same time that the feed is stopped

by the transfer of air in the manner described, the compression of

the air in another small dome in the same pit has forced a water seal

on the air-pipe leading from this dome to the feed in the next bed,

and thus liberates the air-lock in the feed of that bed and allows

the sewage to flow to this in rotation. The whole operation is then

repeated with each bed in rotation, the last bed in the series, when

full, starting the feed in the first bed again. These same feeds may

be arranged to hold up sewage in a collecting or dosing tank, so as to

ensure the accumulation of sufficient sewage to fill each bed at one

dose within a reasonable time.

[Illustration: FIG. 141.—CONTACT BED APPARATUS.]

In order to ensure that the sewage is held up in each bed for a

suitable period for contact, the outlet is provided with an automatic

syphon, which is arranged in such a way that the filling of the bed

alone can start it. When the bed is full, the sewage flows through a

pipe with an adjustable orifice into the timing pit. When this pit is

full, the compression of the air in a small dome placed in the pit, and

connected to the syphon by means of an air-pipe, releases the air in

the syphon and allows it to start at the end of the desired period

of contact. A special feature of these syphons is that they are so

arranged that after they have emptied the bed they continue in action

as syphons, taking the drainings from the bed, however small in volume

they may be, and stopping off only when the bed commences to fill

again, thus ensuring a thorough draining of the material. Another

special feature of this apparatus is that there are no moving parts,

the whole operation depending upon the transfer of air by means of the

head of liquid. It is important to note that by this apparatus the

period of contact in any bed can be arranged for any particular length

of time, quite irrespective of the rate of flow of the sewage to the

works, and independent of the filling and emptying of the other beds in

the series.

[Illustration: FIG. 142.—CONTACT BED APPARATUS.]

[Illustration: FIG. 143.—CONTACT BED APPARATUS.]

[Illustration: FIG. 143_a_.—CONTACT BED APPARATUS.]

Another apparatus which has been used largely in the past is that

supplied by the Septic Tank Company, Ltd. This apparatus is made in two

forms, illustrated in Figs. 141 and 142. The chief difference between

the two types is that in the one case, Fig. 141, the period of contact

is controlled by the filling of the next bed, and is thus dependent

upon the rate of flow of the sewage, while in the other case, Fig.

142, the period of contact is “timed” for from one to two hours, and

is independent of the rate of flow of the sewage. In both cases each

set of gear is built up on its own bed-plate, and comprises the inlet

and outlet valves and the connecting pipes to and from the same. The

valves are of the simple spindle-type, and are connected by rods to

rocking levers and actuated by buckets or floats, working in chambers

or pits which are in communication with the different beds. By means

of overflows from the beds to the buckets, and other devices, the

various portions of the gear are actuated in such a manner that they

automatically fill the several beds in each set in regular rotation,

hold them full for contact, and eventually discharge the treated liquid

to the effluent drain. Full details of the method of operation can be

obtained from the manufacturers, who claim that the gear will work

satisfactorily without attention other than the oiling of the bearings

and joints every few weeks.

Another type of automatic apparatus for contact beds is that

manufactured by Messrs. J. Blakeborough and Sons, as used in the Triple

Tank System of sewage treatment, Fig. 143. In this case the beds are

arranged in sets of three, and the filling of each is effected by the

overflow from the last bed filled, the discharge being effected by the

rising of the liquid in the last bed filled. The apparatus consists

broadly of a slide-valve controlling the outlet-pipe, and connected by

levers to floating cylinders located in separate chambers. One chamber

controls the opening and the other the closing of the valve. The outlet

is provided with a rising and falling arm, which is connected by a

lever to a balance float fixed in a chamber, and coupled by means of a

pipe to the float-chamber of another bed. The method of operation is us

follows:—The tank effluent flows by gravitation to bed A, the filtered

effluent thus rising in outlet chamber A, and also in the overflow

chamber which is connected by pipes to outlet chamber A. As soon as bed

A becomes full, the filtered effluent overflows into closing chamber

A, which is coupled by a pipe to opening chamber B, and the floating

cylinders in each case are raised, with the result that the valve of

bed A closes and the valve of bed B opens, the liquid thus commencing

to run on to bed B. The same action as above is repeated when bed B is

full, and bed C is to be filled, whilst bed C in turn is coupled to bed

B, so that the triple action is repeated over and over again so long as

sewage continues to flow to the beds. As bed A fills, the liquid rises

in outlet chamber A, and, this being coupled to float chamber C, the

liquid rises to a corresponding height in float chamber C. Some time

elapses before the liquid rises to such a height in the float chamber

as to sink the mouth of the outlet pipe below the surface of the liquid

in the outlet chamber, this space of time (which can be regulated as

desired) representing the length of time that the bed is allowed to

stand full before commencing to empty. When the liquid has risen to

a given height in float chamber C, the balance float is raised, this

action tipping the lever and lowering the rising and falling outlet

pipe in outlet chamber C, thus drawing off the effluent from the top

slowly, and without disturbing the whole contents of the bed. (_Note_:

Bed C is assumed to be full). After the liquid in the bed has been

drawn off, the rising and falling outlet pipe remains stationary at the

bottom of the chamber until the next action takes place, which is as

follows:—When bed A becomes full, it is allowed to stand full until

the liquid in bed B (now filling) has risen to a given height, when it

raises the balance float in the float chamber A in a similar manner as

described above, and thus empties the bed A, at the same time emptying

the float chamber C, in which is fixed the balance float connected to

the rising and falling outlet pipe of the bed C (now standing empty),

thus raising the outlet pipe and rendering the bed again ready for use.

[Illustration: FIG. 144.—CONTACT BED APPARATUS.]

[Illustration: FIG. 144_a_.—CONTACT BED APPARATUS.]

Messrs. Glenfield and Kennedy, Ltd., also manufacture apparatus for

operating contact beds, as shown in Fig. 144. This arrangement of

the apparatus delivers the sewage to six beds. There are two valve

boxes, A, internally divided into three compartments. Three sets of

tube valves, B, on each valve box, control the inlets to the several

compartments of the valve box and also to the beds, which are connected

up to the valve boxes with suitable pipes. As the sewage collects in

the measuring chambers, it raises the float C—the float chamber being

in communication—which, through the rack-and-pinion shown, turns the

shaft D. To a sleeve, E, over the shaft D, a hammer, F, is keyed, while

a stopper catch, G, is mounted freely. Keyed to the shaft D are lifting

levers H and K. The lever K lifts the hammer F to the vertical, and,

being free to rotate with the sleeve E, it falls and strikes on one

of the copper buffers, L, in the turning plate M, causing it to turn.

In like manner the stopper catch G is thrown over by the lifter H—a

little in advance of the hammer—and, resting on the stopper plate N,

drops into one of the notches, O, thus stopping the gear at the proper

place. The turning of plate N causes the roller lever P, keyed to the

vertical shaft Q, to rotate—through the agency of the mitre gearing

and horizontal shaft—thus actuating the lever R, and raising the tube

valve B. Two valves are operated simultaneously, one on each valve box.

The valves are held open by the levers P, until, the water being

run off, the weight of the float descending puts the gear in motion

again—by returning the hammer to its original side—and moves the

roller levers P off the end of the levers R, thus allowing the tube

valves B to close and the water to collect once again. The force of

the blow of the hammer as it strikes the buffer L can be regulated

within certain limits, for, on the outer end of the sleeve E carrying

the hammer, a lever, S is keyed, which, as it works in unison with the

hammer, and is attached to the piston of the swivel cataract adjustable

oil cylinder T, has the effect of cushioning the fall of the hammer.

Another type of syphonic apparatus for contact beds is manufactured

by Messrs. Burn Bros., as shown in Fig. 145. In this case the primary

filters are usually supplied with sewage from a collecting or dosing

tank in which two or more discharge syphons are fixed, or they may be

filled from a supply channel under certain circumstances. In the former

case a syphon discharges immediately the collecting tank is full. A

“Sequela” relief apparatus is attached to each syphon, and causes

these to discharge alternately or in rotation. The relief apparatus is

divided into three compartments, and depends for its working on the

transference of oil, of a special nature, from one compartment, A, to

another compartment, C, via compartment B, in stages corresponding

with the number of syphons under control, each relief apparatus at the

commencement being set a stage in advance of the one next to it. After

a syphon has discharged, the oil which has been transferred to the

compartment C in the relief apparatus is automatically returned to the

compartment A, and the apparatus is then ready for another series of

operations. Thus the oil, which is non-evaporative and non-freezing, is

used over again and again, and as it does not come in contact with the

sewage, it remains quite pure and serviceable for years. A discharge

syphon is fixed to each filter, and, in order to ensure a proper period

of contact of the sewage with the filtering material, each syphon

is provided with a “Horometer” relief apparatus. This apparatus can

be set to give a period of contact varying from twenty minutes to

twenty-four hours. The “Horometer,” like the “Sequela,” depends upon

the transference of oil from one compartment to another, but in this

case only two compartments are necessary, A and B. As the filter fills,

the oil is forced, by air pressure, to rise in a vertical pipe from

compartment A above the level of a regulating tap, which is set to pass

the oil into compartment B in the time determined upon for the contact

of the sewage in the filter, and as soon as the necessary quantity of

oil has been transferred through the tap, the syphon discharges. After

the syphon has discharged, the oil is automatically returned from

compartment B to compartment A, and the apparatus is again ready

for use. No watertight brick chambers are required in the filter in

connection with the apparatus, thus effecting considerable economy in

structural work. It is only necessary to construct a screen in dry

brickwork or perforated iron round the syphons to hold up the filtering

material.

[Illustration: FIG. 145.—CONTACT BED APPARATUS.]

[Illustration: FIG. 145_a_.—CONTACT BED APPARATUS.]

The syphons manufactured by Messrs. George Jennings, Ltd., actuated by

air-valves as described under the heading of “Dosing Apparatus,” can

also be adapted for filling and emptying contact beds.

[Illustration: FIG. 146.—CONTACT BED APPARATUS.]

The Enock apparatus for contact beds, Fig. 146, manufactured by

Messrs. A. G. Enock and Co., Ltd., is a simple device working on the

principle of the ball valve. A float, which takes the place of the

ball, is raised by liquid entering a pit, which pit is outside the bed

or tank which has to be emptied by the valve. The valve is attached to

a vertical rod in connection with a horizontal weighted lever, at the

other end of which the float is fixed. When a tank is full, it flows

into the float chamber, and the rise of the liquid in this pit lifts

the float and opens the valve, thereby allowing the contents of the

tank to escape. The float pit then slowly empties itself by means of a

small outlet pipe, and the valve closes so that the tank is ready to

receive more liquid. This apparatus can be arranged so as to fill a

number of beds in rotation, the inlet valve to each pit being either

opened or closed as required by the overflow of liquid from each

contact bed in turn. The outlet valves to the contact beds are similar

to those already described and if the first beds are filled in

rotation, no further connection between the apparatus in the lower beds

will be required, each valve working absolutely independently of the

others.

The chief advantage claimed for this type of apparatus is, that it

can be adjusted so as to suit any required level of liquid in any

particular bed.

_CAPACITY OF PERCOLATING FILTERS AND CONTACT BEDS._

Although this separate section is devoted to the question of

calculating the capacities of percolating filters and contact beds, it

is mainly for the purpose of stating that it is impossible to formulate

any rules which admit of general application. It may reasonably be

pointed out that this last statement is a truism, and affords no

assistance to those in search of information on the subject. There is,

however, so great a tendency in some quarters, to rely upon results

obtained in one place under certain conditions as a guide in designing

a scheme in another place under possibly totally different conditions,

that it is impossible to repeat the statement in question too often.

In the first place, long and practical experience is necessary to

enable an engineer to come to a decision as to what are the conditions

under which any particular scheme is to be carried out, and which

of them will have a bearing upon the methods to be adopted in the

design of the works. A careful study of the fifth report of the Royal

Commission on Sewage Disposal, will show that they assume over 70

different sets of conditions under which percolating filters and

contact beds may be adopted. The capacity of the filters required to

produce the desired results will depend upon the strength of the sewage

to be treated, the type of tank adopted for the preliminary process of

sedimentation, the grade of material to be used, the amount of fall

available, the final destination of the effluent, and other factors, all

of which again may be affected by other circumstances, which must of

necessity be taken into consideration. As the basis for calculating the

capacity of filters may vary between 15 and 200 gallons of the daily

dry-weather flow per cubic yard of material, it is evident that there

is a wide margin for error, and the only safe course to adopt is to

allow for the worst possible conditions and thus provide a large margin

of safety. Although the suggestions made in the fifth report of the

Royal Commission with regard to the provision to be made under various

sets of conditions may be taken as a guide, to some extent, it should

be borne in mind that the figures given represent the minimum which

should be allowed in each case, and the only really safe guide in these

matters is long practical experience of a large number of works under

the greatest possible variety of conditions.

In order, however, to provide a rough guide for the purpose of making

preliminary estimates, it may be stated here that, under ordinary

conditions, with sewage of average strength, a properly designed

preliminary process, suitable material of medium grade, and not less

than 4 feet deep for percolating filters, it should be possible to

produce an effluent which will not create a nuisance by providing—

(_a_) Percolating filters, at the rate of one cubic yard

for every 84 gallons of the daily dry-weather volume, or

(_b_) Contact beds, at the rate of one cubic yard in each

series for every 56 gallons of the daily dry-weather volume.

In other words, the ratio of the cubic capacity of filter material to

the daily dry-weather volume of the sewage for all ordinary purposes

may be taken as—

(_a_) 2 to 1 for percolating filters.

(_b_) 3 to 1 for contact beds.

TABLE, GIVING THE RATIO OF THE TOTAL CUBIC CAPACITY OF PERCOLATING

FILTERS AND CONTACT BEDS TO THE DAILY DRY-WEATHER VOLUME OF THE SEWAGE

UNDER VARYING CONDITIONS.

──────────────────────────┬──────────────────────────────────────

│ Percolating Filters

├──────────────────────────────────────

│ Strength of Sewage

├────────────┬────────────┬────────────

│ Strong │ Average │ Weak

├────────────┴────────────┴────────────

Preliminary Process. │ Grade of Material

(See pages 23, 29). ├──────┬─────┬──────┬─────┬──────┬─────

│Coarse│ │Coarse│ │Coarse│

│ or │ Fine│ or │ Fine│ or │ Fine

│medium│ │medium│ │medium│

──────────────────────────┼──────┼─────┼──────┼─────┼──────┼─────

Detritus tanks │11·20 │ — │ 6·72 │ — │ 4·20 │ —

│ │ │ │ │ │

Septic tanks │ 3·73 │ — │ 2·40 │ — │ 1·68 │ 1·68

│ │ │ │ │ │

Continuous flow settlement│ 3·73 │ — │ 2·40 │ — │ 1·68 │ 1·68

│ │ │ │ │ │

Quiescent settlement │ 3·36 │ 6·72│ 1·68 │ 2·40│ 1·29 │ 1·29

│ │ │ │ │ │

Continuous flow chemical }│ │ │ │ │ │

precipitation }│ 2·58 │ 3·36│ 1·68 │ 2·10│ 1·12 │ 0·96

│ │ │ │ │ │

Quiescent chemical }│ │ │ │ │ │

precipitation }│ 1·68 │ 2·58│ 1·29 │ 1·29│ 0·98 │ 0·84

──────────────────────────┴──────┴─────┴──────┴─────┴──────┴─────

──────────────────────────┬───────────────────────────────────────────

│ Contact Beds

├───────────────────────────────────────────

│ Strength of Sewage

├──────────────┬──────────────┬─────────────

│ Strong │ Average │ Weak

├──────────────┴──────────────┴─────────────

Preliminary Process. │ Number of Series

(See pages 23, 29). ├────┬────┬────┬────┬────┬────┬────┬────┬───

│ │ │ │ │ │ │ │ │

│ ×1 │ ×2 │ ×3 │ ×1 │ ×2 │ ×3 │ ×1 │ ×2 │ ×3

│ │ │ │ │ │ │ │ │

──────────────────────────┼────┼────┼────┼────┼────┼────┼────┼────┼───

Detritus tanks │ — │ — │6·72│ — │6·72│ — │ — │4·42│ —

│ │ │ │ │ │ │ │ │

Septic tanks │ — │ — │5·09│ — │4·42│ — │2·24│2·54│ —

│ │ │ │ │ │ │ │ │

Continuous flow settlement│ — │ — │5·09│ — │4·42│ — │2·24│2·54│ —

│ │ │ │ │ │ │ │ │

Quiescent settlement │ — │ — │3·81│ — │3·36│ — │1·68│ — │ —

│ │ │ │ │ │ │ │ │

Continuous flow chemical }│ │ │ │ │ │ │ │ │

precipitation }│ — │5·09│ — │ — │3·36│ — │1·26│ — │ —

│ │ │ │ │ │ │ │ │

Quiescent chemical }│ │ │ │ │ │ │ │ │

precipitation }│ — │3·90│ — │ — │2·54│ — │1·26│ — │ —

──────────────────────────┴────┴────┴────┴────┴────┴────┴────┴────┴───

KEY: ×1 = Single

×2 = Double

×3 = Triple

In the case of contact beds these figures give the cubic capacity of

each series, and they must be doubled or trebled respectively for

double and triple contact. Both percolating filters and contact beds,

constructed on this basis, would be capable of treating up to three

times the dry-weather flow in times of storm.

Having given the above method of calculation, in a form not usually

adopted in connection with sewage disposal, and bearing in mind the

misunderstandings which frequently arise in comparing the various

methods in use at the present time in different countries, it may be

useful to set out in this form the figures which, it is understood,

have been adopted by the Local Government Board, on the basis of

the fifth report of the Royal Commission on Sewage Disposal, as the

minimum which they consider suitable under varying conditions. In the

Table opposite, the figures given represent the ratio which the cubic

capacity of the filters bears to the daily dry-weather volume of the

sewage, whether it be in gallons, cubic feet, cubic metres, vedros, or

any other term of measurement.

_Examples._—1. A daily dry-weather volume of 10,000 gallons

of sewage, of average strength, is to be treated upon

percolating filters of medium sized material, after

preliminary treatment in septic tanks.

10,000 gallons × 2·40 = 24,000 gallons

= 3,840 cubic feet

= total cubic capacity of filters

2. A daily dry-weather volume of 3,000 cubic metres of weak

sewage is to be treated upon single contact beds, after

preliminary treatment in continuous flow settlement tanks.

3,000 cubic metres × 2·24 = 6,720 cubic metres

= total cubic capacity of beds

For the purpose of the above Table, the strength of the sewage is

estimated according to the amount of oxygen absorbed from permanganate

of potash in four hours, as indicated in the fifth report of the Royal

Commission as follows:—

Parts per 100,000

“Strong” sewage = oxygen absorbed 17 to 25

“Average” ” = ” ” 10 to 12

“Weak” ” = ” ” 7 to 8

A quick method of converting gallons into cubic feet is to multiply the

gallons by the reciprocal 0·16. This can be done rapidly (frequently by

mental calculation) by multiplying the gallons by 4, and the product

again by 4, and inserting the decimal point between the second and

third figures from the right-hand side, thus:—

24,000 × 4 = 96,000 × 4 = 384,000 = 3840·00

= cubic feet

This is useful in calculating the capacity of tanks, and for all similar

purposes.

_STORM-WATER TREATMENT._

In connection with Sewage Disposal Works, the term “storm-water” is

generally understood to mean the extra volume which reaches the works

in times of rainfall, in excess of three times, up to and including

six times, the average dry-weather flow; so that the volume of

storm-water for which provision should be made is equal to three times

(volumes) the daily dry-weather flow. Prior to the publication of the

fifth report of the Royal Commission, it was usual to provide a rough

straining filter for the storm-water, or to reserve a portion of the

land for the purpose of dealing with it by broad irrigation. In either

case the area of filter surface or land required was 1 superficial yard

for every 500 gallons of storm-water (D.W.F. × 3/500 = super-yards).

As the result of their investigations, the Royal Commission came to the

conclusion that “storm-water” filters, as generally constructed under

these conditions, were useless for the purpose for which they were

required, and this confirmed the views of most engineers of experience.

Where suitable land can be secured for the purpose, and arranged in

such a manner that it is reserved solely and entirely for treating the

storm-water, this method may still be adopted. If this is not possible,

stand-by tanks may be constructed for the purpose of receiving the

storm-water. These tanks are to be not less than two in number, and

should have a total capacity of not less than one-quarter of the

average daily dry-weather flow. The only overflow at the outfall works

from which storm-water may be discharged direct to the stream, or other

final effluent outlet, must be from these stand-by tanks, and it should

not come into operation until these tanks are full. Having regard to

these recommendations, it is necessary in every scheme to provide at

least two special storm-water stand-by tanks, with a total capacity of

¼ D.W.F.; and the drawing, Fig. 147, illustrates a simple method of

constructing these. In this case the inlets are in the form of weirs,

running the full width of the tank, so that if the channel leading to

these tanks is in communication with, and at the same level as, the

inlets to the detritus tanks, and the latter are provided with slotted

doors (see Fig. 10, page 19), the weir at the inlets to the stand-by

tanks will act as the actual storm-overflow, and, being of considerable

length, the maximum height to which the water will rise in passing over

this weir will be very small, and will thus have very little effect

upon the rate of flow to the sedimentation tanks.

As the only overflow discharging direct to the stream must be from

these tanks, and must only come into operation when they are full,

the outlet is also constructed in the form of a weir discharging into

a channel from which a pipe would be laid to the stream. A further

requirement in connection with these tanks is that they should always

be kept empty, ready to receive the excess of storm-water at any time.

From this it is evident, that these tanks must be emptied after each

heavy shower or storm which increases the rate of flow of sewage to

the works beyond three times the dry-weather flow. Unfortunately,

no directions are given as to the manner in which this is to be

accomplished. In the absence of any definite statement to the contrary,

it might be inferred that, after the overflow from these tanks has

ceased, their contents may also be discharged direct to the stream. As,

however, this would necessitate outlets at or near the bottom of the

tanks, there would appear to be a possibility of the suspended matters

deposited in the tanks being discharged to the stream—the very thing

the tanks are designed to prevent. With such an arrangement, also,

there will be a risk of the man in charge of the works, either wilfully

or by an oversight, leaving the outlets at the bottom of the tanks

open, and thus permitting the storm-water to pass direct to the stream

without the settlement which it is anticipated by the Royal Commission

(Fifth Report, page 233, par. 352) will be provided for all storm-water

arriving at the works.

[Illustration: FIG. 147.—STORM-WATER STAND-BY TANKS.]

It is obvious that these tanks must be emptied after every heavy shower

or storm, and that facilities must be provided both for drawing off the

supernatant water and for removing the deposit which will accumulate at

the bottom. In the author’s opinion, the only safe method is to provide

floating arm outlets for the supernatant water, and to discharge this

to land or to a special filter for further treatment, or, better still,

to pump it up to the detritus tanks to be treated again with the

ordinary sewage. In schemes where the whole of the sewage is pumped

at the works, the contents of these storm-water stand-by tanks should

certainly be discharged into the pump-well, as this would not involve

the provision of special pumping plant. With regard to the sludge from

these tanks, this should be drawn off by means of special outlets, and

dealt with on sludge draining beds in the manner previously described

(page 83).

The difficulties which frequently arise in designing suitable and

convenient methods of dealing with storm-water, render it desirable

that very careful consideration should be given to the question as to

whether it would not be more satisfactory, from the point of view of

both economy and efficiency, to omit the stand-by tanks, and increase

the capacity of the filters required to deal with the _ordinary_ sewage,

to such an extent that they will be capable of dealing with the

whole volume of sewage and storm-water combined up to six times the

dry-weather flow, and thus obviate the necessity for any storm-overflow

at all at the outfall works. If this idea were universally adopted,

it would necessitate greater care in the construction of any

storm-overflow required on the line of the outfall sewer itself before

it reaches the works, but there are (or should be if the sewers were

properly constructed) so few cases where the excess of flow, even

during the heaviest rainfall, ever reaches six times the dry-weather

flow, that the extra cost involved cannot be considered excessive if

the greater certainty of securing satisfactory results at all times is

taken into consideration.

_MEASURING APPARATUS._

In recent years the provision of proper means of measuring and

recording the flow of sewage at disposal works is becoming more

general, but there are still a very large number of works at which it

is impossible to obtain any trustworthy information as to the volume

of sewage treated. As long as all works smoothly, and there is no

trouble with the effluent, it is considered superfluous to trouble

about the quantity of the liquid which passes through. When, however,

difficulties arise, and it becomes necessary to investigate the cause

of the trouble, it is of the utmost importance to be in a position to

ascertain the daily volume of the sewage arriving at the works and the

variations in the rate of flow, as well as the quantities dealt with

by each separate tank and filter. It is also of great assistance, in

making investigations at such times, to have a definite record of the

volumes treated day by day during the preceding six months; indeed the

possession of a complete record of the daily flow of sewage over the

whole period during which a sewage works has been in operation, is a

valuable asset not only to those responsible for the works themselves

but also to the authorities who control the streams and watercourses,

and to investigators in search of information to be used for the

public benefit. The initial cost of suitable measuring and recording

appliances is not excessive, but, when once the works are completed

and in good working order, the local surveyor or manager has great

difficulty, and usually finds it impossible, to persuade his committee

that the outlay is justified. It is, therefore, desirable that

engineers should in all cases make provision for such apparatus in the

contract for the construction of the works, and thus make sure that it

will be available when required.

[Illustration: FIG. 148.—GAUGE WEIR PENSTOCKS.]

Various types of measuring appliances are in use. Among these the

simplest is the gauge weir penstock Fig. 148, manufactured by Messrs.

Adams Hydraulics, Ltd., from which the depth of water flowing over the

weir can be observed at any time. This, however, does not provide a

record of the volume flowing at all times. For this purpose the same

firm supply several types of recorders, among which the simplest is the

type shown in Fig. 149. This is supplied with 24-hour or 7-day

movement, and charts which register the volume in gallons per minute,

per hour, or per 24 hours.

[Illustration: FIG. 149.—RECORDING APPARATUS.]

Another measuring apparatus is that supplied by Messrs. George

Jennings, Ltd., Fig. 150. This consists briefly of a hollow copper

float attached to a brass rod, which is carried up through a hollow

column into the indicator box provided with a glass hinged door. The

brass rod is provided with pointers, which move up and down with the

rods and indicate the water level.

[Illustration: FIG. 149_a_.—VOLUME RECORDER.]

Messrs. George Kent, Ltd., supply a large number of various types of

recorders and measuring instruments, including the well-known “Venturi”

meter and others actuated by floats to indicate the discharge over a

weir. The Venturi meter type of measuring apparatus adapted for sewage,

is shown in Fig. 151. In this case the Venturi tube may form part of

the ordinary supply pipe, or it may be fitted in a chamber built in the

supply channel, the tube connected through the chamber with its ends

terminating in the channel at either side. This measuring apparatus may

be fitted with the following types of recorders. A diagram only,

counter only, or combined counter and diagram in one instrument. The

recorder may be placed in any convenient position within a thousand

feet of the meter tube.

[Illustration: FIG. 150.—MEASURING APPARATUS.]

[Illustration: FIG. 151.-THE “VENTURI” METER.]

[Illustration: FIG. 152.—MEASURING APPARATUS.]

Several types of measuring apparatus are manufactured by Messrs.

Glenfield and Kennedy. One of these is illustrated in Fig. 152. This

consists of an apparatus for recording the volume of water or sewage

flowing over a weir, a chart being revolved by clockwork, and the

volume indicated by a pen actuated by a float and cord working over

pulleys. This instrument can be fitted with cam and pen carriage to

show the rate of discharge on the chart (24 hours or 7 days), in

gallons of cubic feet per minute over a V-notch, rectangular weir, or

in an open channel of known dimensions. It is claimed that by simply

taking the area of the diagram, the total discharge for any period can

be ascertained much more quickly and more correctly than from a diagram

simply giving the height flowing over the weir.

A somewhat novel form of apparatus, recently introduced by Messrs.

Adams Hydraulics, Ltd., for measuring the flow of sewage in a channel,

consists of a water-wheel by means of which the velocity of the flow is

registered. In order to maintain the paddles of the wheel at a uniform

depth below the surface of the liquid, the wheel is carried upon a

shaft supported by two floats provided with vertical guide rods working

in brackets attached to the sides of the channel. By this means the

whole of the apparatus rises and falls with the liquid in the channel.

The wheel-shaft is provided with a bevel-toothed wheel, which engages

with another similar wheel attached to a flexible shaft, and this

drives a set of geared wheels similar to a flush-tank counter, which

thus record the number of revolutions made by the paddle-wheel.

_STERILISATION OF SEWAGE EFFLUENTS._

It has been recognised in many quarters that, although it is possible

by modern methods of sewage disposal to secure a high degree of

purification from a chemical point of view, it may be necessary in

certain cases to take steps to remove the large numbers of bacteria

present in all such effluents. Experiments have been made which

demonstrate that, when a pure culture of some specific organism is

added to a sewage in a sufficiently large quantity, it may pass through

the tanks and filters, and appear in the final effluent. This result

is not necessarily a conclusive proof that the bacteria in sewage

effluents are dangerous, as the experiments do not represent normal

practical conditions. On the other hand, it is true that, in ordinary

practice, sewage effluents contain large numbers of _B. coli_, which is

admittedly of intestinal derivation, and although this bacillus is not

a disease organism itself, its survival in an effluent is considered

an indication of the presence of sewage matter, and consequently

of the possibility of the survival of any pathogenic germs which

may be present in the crude sewage. On this basis, scientists argue

that sewage effluents are _potentially_ dangerous—that there is a

possibility of the pollution of drinking-water or shell-fish by the

bacteria present in sewage effluents. This being so, it is evident that

an additional process will, in some cases, be required to remove the

bacteria, and in a few cases sand filters have been provided for this

purpose. These, however, involve a comparatively high initial expense,

and a considerable annual outlay for maintenance, and in some quarters

it is considered that sterilisation may possibly be a means of securing

the desired result at less cost, and with a higher percentage of

removal of bacteria, and consequently with a higher degree of safety.

It is true that a number of scientists, in replying to a question which

was submitted to them on this subject by the Royal Commission on Sewage

Disposal, stated that in their opinion sterilisation was impracticable,

but this was in the year 1903, and there is good reason for assuming

that if the same question were put to the same men to-day, the replies

would in many cases be modified, if not entirely different. Practical

experiments in the sterilisation of sewage effluents have been few

and far between in this country, but in the United States of America

a large number of reliable experiments under varying conditions have

been made, and the results published. From these it is evident that

sterilisation is not only possible, but economically practicable.

Unfortunately, both in America and elsewhere, attempts were made to

sterilise crude sewage and tank effluents, and the results of these

experiments were so unsatisfactory, both in efficiency and cost, that

they gave the impression that sterilisation was impracticable.

In the opinion of the author, sterilisation should be restricted to the

destruction of living organisms, and should only be used in the case

of liquids with a high degree of chemical purity, and a low content

of matters in suspension. It is quite possible at the present time

to produce sewage effluents which comply with these conditions, by

means of properly designed, constructed and managed sewage disposal

works, as long as these include suitable effluent settling tanks

for the removal of the solids in suspension. Effluents which comply

with the provisional standard suggested by the Royal Commission, and

drinking-water supplies which are very slightly polluted, would be very

suitable.

A number of different methods of sterilisation have been tried, but so

far as the existing knowledge of the subject extends, the application

of chlorine in one form or another is generally admitted to be the most

efficient and economical process. The chlorine may be applied in the

form of a solution of chloride of lime, or as a hypochlorite of sodium,

or of magnesium. The solution of chloride of lime may be prepared by

the sewage works manager, but this necessitates a considerable amount

of care and knowledge in order to secure the correct strength at all

times, and it is, of course, essential that the chloride of lime itself

should always be of a known strength. The hypochlorite of sodium may be

produced chemically, and this can be purchased of known strength from

chemical manufacturers. For large volumes of sewage effluent, however,

it will probably be found most economical to utilise an electrically

produced hypochlorite of sodium, as this can be prepared on the works

as and when required, of a uniform strength, and at a comparatively low

cost.

In the case of the Digby process, briefly stated, this consists in

passing an electric current through a solution of sodium chloride, with

the result that the sodium chloride is broken up into its component

parts, and chlorine is liberated at the positive pole, while sodium is

deposited at the negative pole. The sodium and the chlorine are then

allowed to recombine in the form of hypochlorite, and this solution

is then ready for application to the liquid to be sterilised. Other

processes are similar in principle but vary in detail.

[Illustration: FIG. 153.—THE DIGBY MERIDIONISER.]

This process naturally involves the use of an electric current and

an apparatus for producing the hypochlorite. Of the latter there are

several on the market, and an illustration of the Digby Meridioniser,

which is manufactured and supplied by Messrs. Adams Hydraulics, Ltd.,

is given in Fig. 153. The particular feature of this apparatus consists

in the manner in which the re-combination of the anode and cathode

products are secured. Instead of the re-combination taking place in the

main body of the electrolyte, it can only take place in the special

porous compartment enclosing the electrodes. The re-combination may

take place in either the anode or the cathode compartment, the products

of the one compartment being conveyed to the other compartment. Thus

the caustic hydrate from the cathode cells flows by gravity into the

anode compartment, the two compartments being connected by a glass

pipe. Fresh water or water containing an excess of alkali is run into

the cathode cell. This process gives hypochlorite solution of low

saline content, the only salt present in the resultant liquor being

that due to diffusion, depending upon the porosity of the closely

covering compartment walls, or upon such a reaction as that covered

by the Blount hypothesis. A cross-section of this apparatus is shown

at Fig. 153, in which A is the positive lead; BB negative leads, C

outflow, D inflow, EE cathodes, F anode.

Another machine is that supplied by Messrs. Oxychlorides (1907),

Limited. This machine consists essentially of a graphite anode

of circular cross-section (except as to about 4 in. at the top,

which is left open for the free escape of gases evolved during the

electrolysis), and within it a metallic cathode of smaller circular

cross-section. The annular space between the anode and cathode is

filled with a solution of common salt, or with sea-water, through which

a current is passed from a low-potential dynamo. In either case the

ultimate result is to obtain some of the chlorine of the salt in an

active or available form, the only difference being that in the case of

using strong salt solution, a concentrated form of available chlorine

may be obtained, while with sea-water a weaker solution results. Where

sea-water is readily obtainable it is naturally more economical to

make use of it, and to employ the larger volume of less concentration;

while where sea-water is unobtainable and salt is expensive, or where

chlorides in the effluent are objected to, it is more advantageous to

prepare concentrated solutions, and to dilute them when required for

use. This machine is made in various sizes to suit varying conditions.

It was used by the Royal Commission on Sewage Disposal in connection

with their experiments at Guildford, referred to in their Report of

1908, pages 198 to 201.

Electrolytic hypochlorite of magnesium is being produced daily, by the

Borough of Poplar, for use as a disinfectant. The highly effective

qualities of this solution, as well as the low cost of production,

makes it a very valuable disinfectant, and for the results obtained

every credit is due to Dr. F. W. Alexander, the Medical Officer of

Health, who initiated the scheme, and to whose unbounded energy and

enthusiasm the success of the work is due. This solution is, of course,

equally suitable for the sterilisation of sewage effluents. The cost of

production of this solution, of an average strength of from 4·5 to 5

grammes of available chlorine per litre (·45 to ·5 per cent. solution),

is estimated at under one penny per gallon. The apparatus in use at

Poplar has been supplied by the Farringdon Engineering Co., and an

illustration of the plant is shown in Fig. 154.

[Illustration: FIG. 154.—ELECTROLYTIC HYPOCHLORITE OF MAGNESIUM

PLANT.]

It consists of four cells, each containing ten elements, consisting of

one positive and two negative plates. The positive plates consist of

thin platinum wire, wound upon slate slabs, and the negative electrodes

are of zinc. The four cells are placed one above the other, so that

the liquid passes through from one to the other by gravitation. The

feed-tank at the top contains a solution of sodium chloride and

magnesium chloride, and is fitted with a glass gauge to indicate the

amount of solution in the tank. From this tank the solution passes

through a small ball-valve cistern, so as to maintain a constant rate

of flow. The feed-tank is also provided with a plate, operated by a

chain carried over to the outside of the tank, by means of which the

liquid to be electrolysed can be stirred from time to time, so as to

secure a uniform strength of solution. The solution passes through

the four electrolysers in series, being subjected to the action of a

regulated current of 15 to 17 amperes at 230 to 250 volts, being 5·7

to 6·2 volts per cell. After the electrolysed solution leaves the last

cell it runs into a small tank, where a fixed amount of hydroxide of

magnesium is mixed with it, and it is claimed that by this means the

solution is rendered stable, a quality which should be of much value

where the solution has to be stored for any length of time.

The question as to what is the most suitable sterilising agent to use

under certain conditions, and in what proportion it should be added to

the sewage effluent, is a matter for the chemist and biologist. The

method of application is, however, the duty of the engineer. As in the

case of other chemicals, there are two ways in which it may be applied.

The solution may be added to the sewage effluent in equal doses of

varying strength, or in varying doses of equal strength. There is a

third method, involving the variation of the dose and the strength

of the solution, but while this is not impossible it is probably not

practical. The chief difficulty to be overcome is the variation of

both the rate of flow and the strength of the sewage, and the most

practical solution is to prepare the sterilising agent of a uniform

strength, and vary the doses in direct proportion to the flow of the

effluent, the minimum dose being sufficient for the maximum strength

of the sewage. This method was adopted by the author in the case of a

small scheme of sewage disposal, which he prepared for a place where

the only outlet for the final effluent was a discharge over an area of

chalk subsoil, from which the water supply of a large town is drawn. In

this case, he designed a simple apparatus which does not involve any

special appliances, and which would be quite satisfactory for ordinary

practical purposes. A new apparatus for the purpose in question has,

however, recently been introduced by Messrs. Nixon and Mannock. As

will be seen from the illustration, Fig. 155, it is based upon the

application of the Venturi principle, and involves the use of a

Venturi tube, as previously described under the heading of “Measuring

Apparatus.” In fact, the same Venturi tube can be utilised to serve

both for measuring the flow of the effluent, and for applying the

sterilising agent in direct proportion to the flow of the effluent.

[Illustration: FIG. 155.—NIXON AND MANNOCK’S APPARATUS FOR

INJECTING CHEMICAL SOLUTION.]

The apparatus consists of a cylinder C, the top of which is connected

by means of a pipe fitted with a three-way cock to the “Upstream”

end of the tube A. A similar connection is made from the bottom of

the cylinder to the “throat” B. A piston of the type used in the Kent

Standard Water Meters, and provided with a counterbalance weight,

works in the cylinder by means of the difference of the pressure on

the two sides of the Venturi tube. The chemical solution (e.g. a 5

per cent. solution of chlorine) is supplied to the underside of the

piston, and the pressure on the upper side of the piston being greater

than the pressure on the underside, the chemical is forced down by the

piston and injected through the injection tube and regulating valve

into the effluent at the “throat” of the Venturi tube. As the flow

of the effluent through the Venturi tube produces a difference of

pressure which varies as the square root of the velocity, the rate of

injection will also vary in the same proportion. The injection is thus

in exact proportion to the flow, and any variation of the flow will

automatically cause a corresponding variation in the rate of injection.

When the chemical re-agent is exhausted, the piston will be at the

bottom of the cylinder, and the pointer at zero. In order to recharge

the cylinder with the chemical, the three-way cocks must be reversed

by means of the hand lever, thereby cutting off pipes A and B, and

simultaneously connecting the top of the cylinder to the waste pipe,

and the bottom to the supply from the chemical storage tank, which is

fixed at such a height that the head will rapidly force the piston up

and re-fill the cylinder with the chemical. The three-way valves are

then reversed, and the apparatus is again in full working order. The

apparatus shown is applicable to the treatment of 1000 gallons per

hour, and will only need recharging once per day of 24 hours.

A feature of this apparatus is that it is self-starting, and should the

flow cease, the injection will also automatically stop, the static head

on both sides of the piston being equal. There is absolute immunity

from danger or over-injection of the chemical by this system, and

this is a valuable factor in the treatment of potable water. Where

absolutely necessary, the same firm can supply a de-chlorinating

apparatus. By means of the indicator, the works manager is constantly

informed of the exact amount of chemical injected, and the scale

readings can be compared with those of a Venturi Meter operated by the

same Venturi tube. This apparatus can be supplied of a larger size, and

provided with automatic recharging gear for larger installations.

Whatever method may be adopted for applying the sterilising agent, it

is essential in all cases to have a storage tank to receive the mixture

in order to provide time for the chemical to have full effect. So far

as can be ascertained at present, a storage capacity equal to one

hour’s flow of the liquid to be sterilised will be sufficient under

ordinary circumstances, but provision should be made for thoroughly

mixing the chemical with the effluent and for drawing off any deposit

which may occur in the tank without interfering with the normal working

of the plant.

Although the present volume is devoted entirely to the disposal of

sewage, it may be stated here that in the matter of sterilisation,

the suggestions that have been made apply with equal force to

drinking-water supplies. Where the water contains a considerable amount

of matter in suspension, it would be advisable to provide means for

ample storage and settlement before passing it through the sterilising

plant.

_Note._—An apparatus for the injection of chlorine

solutions for the purpose of sterilising sewage effluents

and drinking water has recently been brought out by the

Candy Filter Co., Ltd., and has for some months been in

practical operation, dealing with 200,000 gallons of river

water per day for an important municipal waterworks in

the country. In this case the installation includes a

de-chlorinating process, and it is stated that the results

of tests in actual work show that the sterilised water

contains neither _B. coli_ nor free chlorine.