CONSTRUCTION

=Supporting the Chimney=

Stable foundations, preferably of concrete, should be provided, at least

6 inches wider all around than the chimney and 8 inches thick for

one-story and 12 inches thick for two-story houses. When there is no

basement or cellar (fig. 7, _A_), start the foundation of an exterior

chimney well below the frost line; otherwise, extend the base to the same

level as the bottom of the foundation of the building. Foundations for

tall, heavy chimneys require special consideration.

Where the wall of the house is of solid masonry 12 inches or more thick,

the chimney may be offset and carried on corbels or masonry brackets

instead of being carried down to the ground. The offset should not extend

more than 8 inches from the face of the wall, each course projecting not

more than 1 inch, and should not be less than 12 inches high. Often the

corbeling is started at the second- or third-floor level so that the

chimney is only one or two stories high.

[Illustration: Figure 8.--For structural safety the amount of offset must

be limited so that the center line, XY, of the upper flue will not fall

beyond the center of the wall of the lower flue. _A_, Offsetting of the

left wall of an unlined flue is started two brick courses higher than

on the right wall so that the area of the sloping section will not be

reduced after plastering; _B_, a lined flue showing the method of cutting

the tile.]

Chimneys in frame buildings should be built from the ground up or should

rest on the foundation or basement walls if of solid masonry 12 inches or

more thick.

A chimney resting on or carried by wooden floors, beams, or brackets or

hung from wooden rafters (fig. 7, _B_) is a fire hazard. Wood framing

shrinks, and beams supporting heavy loads deflect in time. Sagging beams

injure the walls and ceilings of the house and are apt to crack the

chimney, rendering it dangerous.

=Flue Linings=

Although, to save expense, chimneys are built without flue lining, those

with linings are more efficient. When the flue is not lined, the mortar

and bricks directly exposed to the action of fuel gases disintegrate.

This disintegration and that occurring from changes in temperature

frequently cause cracks in the masonry, thereby reducing the draft. An

unlined chimney is best if not plastered except at the sloped section

(fig. 8, _A_). However, the vertical and horizontal joints should be

filled with mortar and struck smooth and flush with the wall. Offsets or

bends in flues (fig. 8) should not be greater than 30° with the vertical.

This slope can be obtained by offsetting or corbeling each brick course

only 1 inch.

Flue lining must withstand rapid fluctuations in temperature and be

resistant to the action of ordinary flue gases. The shapes used as flue

lining should be of fire-clay, with shells not less than five-eighths

of an inch thick, and should be vitrified. As a safeguard against

over-burning and brittleness, the lining should be tested by submersion

in water at room temperature for 24 hours, during which a quantity of

water weighing more than 3 percent of the dry weight of the lining should

not be absorbed. Place each length of flue lining in position, setting

it in cement mortar with the joint struck smooth on the inside, and then

lay the brick around it. If the lining is slipped down after several

courses of brick have been laid, the joints cannot be filled and leakage

is almost sure to result. Fill any spaces between the lining and the

brickwork completely with mortar, especially if the round type of flue is

used.

The lower section of flue lining, unless resting on solid masonry at the

bottom of the flue, should be supported on at least three sides by brick

courses projecting to the inside surface of the lining. When laying brick

and lining, it is advisable to draw up a tight-fitting bag of straw as

the work progresses so as to catch material that might fall and block the

flue.

Where offsets or bends are necessary in lined flues, tight joints can

be made by mitering or cutting equally the ends of abutting sections

(fig. 8, _B_). This can be done if a cement sack of damp sand is stuffed

firmly into the lining and a sharp chisel is tapped with a light hammer

along the line where the cut is desired. If the cutting is done after the

lining is built into the chimney, the lining may be broken and fall out

of place. The hole for the thimble can be cut the same way when a special

thimble section is not used.

The linings commonly used are rectangular or round. Rectangular linings

are better adapted to brick construction than round linings, but the

latter are considered more efficient. The sizes commonly used are

indicated in table 2.

=Wall Thickness=

Walls of chimneys not more than 30 feet high when lined should be 4

inches thick if of brick and reinforced concrete, 8 inches if of hollow

building units, and 12 inches if of stone. Linings may be omitted in

chimneys having walls of reinforced concrete at least 6 inches thick

or of unreinforced concrete or brick at least 8 inches thick, although

lining is desirable in the case of brick construction. Also the outside

wall of a chimney exposed to the weather is best made at least 8 inches

thick.

In chimneys containing three or more flues, building codes generally

require that each group of two flues be separated from the other

single flue or group of two flues by brick divisions or withes not

less than 3¾ inches wide (fig. 9) . Where two flues are grouped

without divisions, joints in the linings of adjacent flues are safer

if staggered at least 7 inches, and particular care should be taken to

have all joints filled with mortar. Individual flues are advisable for

fireplaces and heating furnaces or boilers.