At any section, let

_C_ or _C'_ represent the total concrete compression;

_T_ or _T'_ represent the total steel tension;

_J_ or _J'_ represent the total vertical shear;

_P_ represent the total vertical load for the length, _b_ - _b'_;

and let [Delta] _T_ = _T'_ - _T_ = _C'_ - _C_ represent the total

transverse shear for the length, _b_ - _b'_.

Assuming that the tension cracks extend to the neutral surface, _n n_,

that portion of the beam _C b b' C'_, acts as a cantilever fixed at _a

b_ and _a' b'_, and subjected to the unbalanced steel tension, [Delta]

_T_. The vertical shear, _J_, is carried mainly by the concrete above

the neutral surface, very little of it being carried by the steel

reinforcement. In the case of plain webs, the tension cracks are the

forerunners of the sudden so-called diagonal tension failures produced

by the snapping off, below the neutral surface, of the concrete

cantilevers. The logical method of reinforcing these cantilevers is by

inserting vertical steel in the tension side. The vertical

reinforcement, to be efficient, must be well anchored, both in the top

and in the bottom of the beam. Experience has solved the problem of

doing this by the use of vertical steel in the form of stirrups, that

is, U-shaped rods. The horizontal reinforcement rests in the bottom of

the U.

Sufficient attention has not been paid to the proper anchorage of the

upper ends of the stirrups. They should extend well into the compression

area of the beam, where they should be properly anchored. They should

not be too near the surface of the beam. They must not be too far apart,

and they must be of sufficient cross-section to develop the necessary

tensile forces at not excessive unit stresses. A working tension in the

stirrups which is too high, will produce a local disintegration of the

cantilevers, and give the beam the appearance of failure due to diagonal

tension. Their distribution should follow closely that of the vertical

or horizontal shear in the beam. Practice must rely on experiment for

data as to the size and distribution of stirrups for maximum efficiency.

The maximum shearing stress in a concrete beam is commonly computed by

the equation:

_V_

_v_ = ------------- (1)

7

--- _b_ _d_

8

Where _d_ is the distance from the center of the reinforcing bars to the

surface of the beam in compression:

_b_ = the width of the flange, and

_V_ = the total vertical shear at the section.

This equation gives very erratic results, because it is based on a

continuous web. For a non-continuous web, it should be modified to

_V_

_v_ = ------------- (2)

_K_ _b_ _d_

In this equation _K b d_ represents the concrete area in compression.

The value of _K_ is approximately equal to 0.4.

Three large concrete beams with web reinforcement, tested at the

University of Illinois[K], developed an average maximum shearing

resistance of 215 lb. per sq. in., computed by Equation 1. Equation 2

would give 470 lb. per sq. in.

Three T-beams, having 32 by 3-1/4-in. flanges and 8-in. webs, tested at

the University of Illinois, had maximum shearing resistances of 585,

605, and 370 lb. per. sq. in., respectively.[L] They did not fail in

shear, although they appeared to develop maximum shearing stresses which

were almost three times as high as those in the rectangular beams

mentioned. The concrete and web reinforcement being identical, the

discrepancy must be somewhere else. Based on a non-continuous concrete

web, the shearing resistances become 385, 400, and 244 lb. per sq. in.,

respectively. As none of these failed in shear, the ultimate shearing

resistance of concrete must be considerably higher than any of the

values given.

About thirteen years ago, Professor A. Vierendeel[M] developed the

theory of open-web girder construction. By an open-web girder, the

speaker means a girder which has a lower and upper chord connected by

verticals. Several girders of this type, far exceeding solid girders in

length, have been built. The theory of the open-web girder, assuming the

verticals to be hinged at their lower ends, applies to the concrete beam

reinforced with stirrups. Assuming that the spaces between the verticals

of the girder become continually narrower, they become the tension

cracks of the concrete beam.[N]

JOHN C. OSTRUP, M. AM. SOC. C. E.--The author has rendered a great

service to the Profession in presenting this paper. In his first point

he mentions two designs of reinforced concrete beams and, inferentially,

he condemns a third design to which the speaker will refer later. The

designs mentioned are, first, that of a reinforced concrete beam

arranged in the shape of a rod, with separate concrete blocks placed on

top of it without being connected--such a beam has its strength only in

the rod. It is purely a suspension, or "hog-chain" affair, and the

blocks serve no purpose, but simply increase the load on the rod and its

stresses.

The author's second design is an invention of his own, which the

Profession at large is invited to adopt. This is really the same system

as the first, except that the blocks are continuous and, presumably,

fixed at the ends. When they are so fixed, the concrete will take

compressive stresses and a certain portion of the shear, the remaining

shear being transmitted to the rod from the concrete above it, but only

through friction. Now, the frictional resistance between a steel rod and

a concrete beam is not such as should be depended on in modern

engineering designs.

The third method is that which is used by nearly all competent

designers, and it seems to the speaker that, in condemning the general

practice of current reinforced designs in sixteen points, the author

could have saved himself some time and labor by condemning them all in

one point.

What appears to be the underlying principle of reinforced concrete

design is the adhesion, or bond, between the steel and the concrete, and

it is that which tends to make the two materials act in unison. This is

a point which has not been touched on sufficiently, and one which it was

expected that Mr. Beyer would have brought out, when he illustrated

certain internal static conditions. This principle, in the main, will

cover the author's fifth point, wherein stirrups are mentioned, and

again in the first point, wherein he asks: "Will some advocate of this

type of design please state where this area can be found?"

To understand clearly how concrete acts in conjunction with steel, it is

necessary to analyze the following question: When a steel rod is

embedded in a solid block of concrete, and that rod is put in tension,

what will be the stresses in the rod and the surrounding concrete?

The answer will be illustrated by reference to Fig. 10. It must be

understood that the unit stresses should be selected so that both the

concrete and the steel may be stressed in the same relative ratio.

Assuming the tensile stress in the steel to be 16,000 lb. per sq. in.,

and the bonding value 80 lb., a simple formula will show that the length

of embedment, or that part of the rod which will act, must be equal to

50 diameters of the rod.

[Illustration: FIG. 10.]

When the rod is put in tension, as indicated in Fig. 10, what will be

the stresses in the surrounding concrete? The greatest stress will come

on the rod at the point where it leaves the concrete, where it is a

maximum, and it will decrease from that point inward until the total

stress in the steel has been distributed to the surrounding concrete. At

that point the rod will only be stressed back for a distance equal in

length to 50 diameters, no matter how far beyond that length the rod may

extend.

The distribution of the stress from the steel rod to the concrete can be

represented by a cone, the base of which is at the outer face of the

block, as the stresses will be zero at a point 50 diameters back, and

will increase in a certain ratio out toward the face of the block, and

will also, at all intermediate points, decrease radially outward from

the rod.

The intensity of the maximum stress exerted on the concrete is

represented by the shaded area in Fig. 10, the ordinates, measured

perpendicularly to the rod, indicating the maximum resistance offered by

the concrete at any point.

If the concrete had a constant modulus of elasticity under varying

stress, and if the two materials had the same modulus, the stress

triangle would be bounded by straight lines (shown as dotted lines in

Fig. 10); but as this is not true, the variable moduli will modify the

stress triangle in a manner which will tend to make the boundary lines

resemble parabolic curves.

A triangle thus constructed will represent by scale the intensity of the

stress in the concrete, and if the ordinates indicate stresses greater

than that which the concrete will stand, a portion will be destroyed,

broken off, and nothing more serious will happen than that this stress

triangle will adjust itself, and grip the rod farther back. This process

keeps on until the end of the rod has been reached, when the triangle

will assume a much greater maximum depth as it shortens; or, in other

words, the disintegration of the concrete will take place here very

rapidly, and the rod will be pulled out.

In the author's fourth point he belittles the use of shear rods, and

states: "No hint is given as to whether these bars are in shear or in

tension." As a matter of fact, they are neither in shear nor wholly in

tension, they are simply in bending between the centers of the

compressive resultants, as indicated in Fig. 12, and are, besides,

stressed slightly in tension between these two points.

[Illustration: FIG. 11.]

In Fig. 10 the stress triangle indicates the distribution and the

intensity of the resistance in the concrete to a force acting parallel

to the rod. A similar triangle may be drawn, Fig. 11, showing the

resistance of the rod and the resultant distribution in the concrete to

a force perpendicular to the rod. Here the original force would cause

plain shear in the rod, were the latter fixed in position. Since this

cannot be the case, the force will be resolved into two components, one

of which will cause a tensile stress in the rod and the other will pass

through the centroid of the compressive stress area. This is indicated

in Fig. 11, which, otherwise, is self-explanatory.

[Illustration: FIG. 12.]

Rods are not very often placed in such a position, but where it is

unavoidable, as in construction joints in the middle of slabs or beams,

they serve a very good purpose; but, to obtain the best effect from

them, they should be placed near the center of the slab, as in Fig. 12,

and not near the top, as advocated by some writers.

If the concrete be overstressed at the points where the rod tends to

bend, that is, if the rods are spaced too far apart, disintegration will

follow; and, for this reason, they should be long enough to have more

than 50 diameters gripped by the concrete.

This leads up to the author's seventh point, as to the overstressing of

the concrete at the junction of the diagonal tension rods, or stirrups,

and the bottom reinforcement.

[Illustration: FIG. 13.]

Analogous with the foregoing, it is easy to lay off the stress triangles

and to find the intensity of stress at the maximum points, in fact at

any point, along the tension rods and the bottom chord. This is

indicated in Fig. 13. These stress triangles will start on the rod 50

diameters back from the point in question and, although the author has

indicated in Fig. 1 that only two of the three rods are stressed, there

must of necessity also be some stress in the bottom rod to the left of

the junction, on account of the deformation which takes place in any

beam due to bending. Therefore, all three rods at the point where they

are joined, are under stress, and the triangles can be laid off

accordingly.

It will be noticed that the concrete will resist the compressive

components, not at any specific point, but all along the various rods,

and with the intensities shown by the stress triangles; also, that some

of these triangles will overlap, and, hence, a certain readjustment, or

superimposition, of stresses takes place.

The portion which is laid off below the bottom rods will probably not

act unless there is sufficient concrete below the reinforcing bars and

on the sides, and, as that is not the case in ordinary construction, it

is very probable, as Mr. Goodrich has pointed out, that the concrete

below the rods plays an unimportant part, and that the triangle which is

now shown below the rod should be partially omitted.

The triangles in Fig. 13 show the intensity of stress in the concrete at

any point, or at any section where it is wanted. They show conclusively

where the components are located in the concrete, their relation to the

tensile stresses in the rods, and, furthermore, that they act only in a

general way at right angles to one another. This is in accordance with

the theory of beams, that at any point in the web there are tensile and

compressive stresses of equal intensity, and at right angles to one

another, although in a non-homogeneous web the distribution is somewhat

different.

After having found at the point of junction the intensity of stress, it

is possible to tell whether or not a bond between the stirrups and the

bottom rods is necessary, and it would not seem to be where the stirrups

are vertical.

It would also seem possible to tell in what direction, if any, the bend

in the inclined stirrups should be made. It is to be assumed, although

not expressly stated, that the bends should curve from the center up

toward the end of the beam, but an inspection of the stress triangles,

Fig. 13, will show that the intensity of stress is just as great on the

opposite side, and it is probable that, if any bends were required to

reduce the maximum stress in the concrete, they should as likely be made

on the side nearest the abutment.

From the stress triangles it may also be shown that, if the stirrups

were vertical instead of inclined, the stress in the concrete on both

sides would be practically equal, and that, in consequence, vertical

stirrups are preferable.

The next issue raised by the author is covered in his seventh point, and

relates to bending moments. He states: "* * * bending moments in

so-called continuous beams are juggled to reduce them to what the

designer would like to have them. This has come to be almost a matter of

taste, * * *."

The author seems to imply that such juggling is wrong. As a matter of

fact, it is perfectly allowable and legitimate in every instance of beam

or truss design, that is, from the standpoint of stress distribution,

although this "juggling" is limited in practice by economical

considerations.

In a series of beams supported at the ends, bending moments range from

(_w_ _l^{2}_)/8 at the center of each span to zero at the supports, and,

in a series of cantilevers, from zero at the center of the span to (_w_

_l^{2}_)/8 at the supports. Between these two extremes, the designer can

divide, adjust, or juggle them to his heart's content, provided that in

his design he makes the proper provision for the corresponding shifting

of the points of contra-flexure. If that were not the case, how could

ordinary bridge trusses, which have their maximum bending at the center,

compare with those which, like arches, are assumed to have no bending at

that point?

In his tenth point, the author proposes a method of simple designing by

doing away with the complicated formulas which take account of the

actual co-operation of the two materials. He states that an ideal

design can be obtained in the same manner, that is, with the same

formulas, as for ordinary rectangular beams; but, when he does so, he

evidently fails to remember that the neutral axis is not near the center

of a reinforced concrete beam under stress; in fact, with the percentage

of reinforcement ordinarily used in designing--varying between

three-fourths of 1% to 1-1/2%--the neutral axis, when the beam is

loaded, is shifted from 26 to 10% of the beam depth above the center.

Hence, a low percentage of steel reinforcement will produce a great

shifting of the neutral axis, so that a design based on the formulas

advocated by the author would contain either a waste of materials, an

overstress of the concrete, or an understress of the steel; in fact, an

error in the design of from 10 to 26 per cent. Such errors, indeed, are

not to be recommended by good engineers.

The last point which the speaker will discuss is that of the elastic

arch. The theory of the elastic arch is now so well understood, and it

offers such a simple and, it might be said, elegant and self-checking

solution of the arch design, that it has a great many advantages, and

practically none of the disadvantages of other methods.

The author's statement that the segments of an arch could be made up of

loose blocks and afterward cemented together, cannot be endorsed by the

speaker, for, upon such cementing together, a shifting of the lines of

resistance will take place when the load is applied. The speaker does

not claim that arches are maintained by the cement or mortar joining the

voussoirs together, but that the lines of pressure will be materially

changed, and the same calculations are not applicable to both the

unloaded and the loaded arch.

It is quite true, as the author states, that a few cubic yards of

concrete placed in the ring will strengthen the arch more than a like

amount added to the abutments, provided, however, that this material be

placed properly. No good can result from an attempt to strengthen a

structure by placing the reinforcing material promiscuously. This has

been tried by amateurs in bridge construction, and, in such cases, the

material either increased the distance from the neutral axis to the

extreme fibers, thereby reducing the original section modulus, or caused

a shifting of the neutral axis followed by a large bending moment;

either method weakening the members it had tried to reinforce. In other

words, the mere addition of material does not always strengthen a

structure, unless it is placed in the proper position, and, if so

placed, it should be placed all over commensurately with the stresses,

that is, the unit stresses should be reduced.

The author has criticized reinforced concrete construction on the ground

that the formulas and theories concerning it are not as yet fully

developed. This is quite true, for the simple reason that there are so

many uncertain elements which form their basis: First, the variable

quantity of the modulus of elasticity, which, in the concrete, varies

inversely as the stress; and, second, the fact that the neutral axis in

a reinforced concrete beam under changing stress is migratory. There are

also many other elements of evaluation, which, though of importance, are

uncertain.

Because the formulas are established on certain assumptions is no reason

for condemning them. There are, the speaker might add, few formulas in

the subject of theoretical mechanics which are not based on some

assumption, and as long as the variations are such that their range is

known, perfectly reliable formulas can be deduced and perfectly safe

structures can be built from them.

There are a great many theorists who have recently complained about the

design of reinforced concrete. It seems to the speaker that such

complaints can serve no useful purpose. Reinforced concrete structures

are being built in steadily increasing numbers; they are filling a long

needed place; they are at present rendering great service to mankind;

and they are destined to cover a field of still greater usefulness.

Reinforced concrete will undoubtedly show in the future that the

confidence which most engineers and others now place in it is fully

merited.

HARRY F. PORTER, JUN. AM. SOC. C. E. (by letter).--Mr. Godfrey has

brought forward some interesting and pertinent points, which, in the

main, are well taken; but, in his zealousness, he has fallen into the

error of overpersuading himself of the gravity of some of the points he

would make; on the other hand, he fails to go deeply enough into others,

and some fallacies he leaves untouched. Incidentally, he seems somewhat

unfair to the Profession in general, in which many earnest, able men are

at work on this problem, men who are not mere theorists, but have been

reared in the hard school of practical experience, where refinements of

theory count for little, but common sense in design counts for much--not

to mention those self-sacrificing devotees to the advancement of the

art, the collegiate and laboratory investigators.

Engineers will all agree with Mr. Godfrey that there is much in the

average current practice that is erroneous, much in textbooks that is

misleading if not fallacious, and that there are still many designers

who are unable to think in terms of the new material apart from the

vestures of timber and structural steel, and whose designs, therefore,

are cumbersome and impractical. The writer, however, cannot agree with

the author that the practice is as radically wrong as he seems to think.

Nor is he entirely in accord with Mr. Godfrey in his "constructive

criticism" of those practices in which he concurs, that they are

erroneous.

That Mr. Godfrey can see no use in vertical stirrups or U-bars is

surprising in a practical engineer. One is prompted to ask: "Can the

holder of this opinion ever have gone through the experience of placing

steel in a job, or at least have watched the operation?" If so, he must

have found some use for those little members which he professes to

ignore utterly.

As a matter of fact, U-bars perform the following very useful and

indispensable services:

(_1_).--If properly made and placed, they serve as a saddle in which to

rest the horizontal steel, thereby insuring the correct placing of the

latter during the operation of concreting, not a mean function in a type

of construction so essentially practical. To serve this purpose,

stirrups should be made as shown in Plate III. They should be restrained

in some manner from moving when the concrete strikes them. A very good

way of accomplishing this is to string them on a longitudinal rod,

nested in the bend at the upper end. Mr. Godfrey, in his advocacy of

bowstring bars anchored with washers and nuts at the ends, fails to

indicate how they shall be placed. The writer, from experience in

placing steel, thinks that it would be very difficult, if not

impractical, to place them in this manner; but let a saddle of U-bars be

provided, and the problem is easy.

(_2_).--Stirrups serve also as a tie, to knit the stem of the beam to

its flange--the superimposed slab. The latter, at best, is not too well

attached to the stem by the adhesion of the concrete alone, unassisted

by the steel. T-beams are used very generally, because their

construction has the sanction of common sense, it being impossible to

cast stem and slab so that there will be the same strength in the plane

at the junction of the two as elsewhere, on account of the certainty of

unevenness in settlement, due to the disproportion in their depth. There

is also the likelihood that, in spite of specifications to the contrary,

there will be a time interval between the pouring of the two parts, and

thus a plane of weakness, where, unfortunately, the forces tending to

produce sliding of the upper part of the beam on the lower (horizontal

shear) are a maximum. To offset this tendency, therefore, it is

necessary to have a certain amount of vertical steel, disposed so as to

pass around and under the main reinforcing members and reach well up

into the flange (the slab), thus getting a grip therein of no mean

security. The hooking of the U-bars, as shown in Plate III, affords a

very effective grip in the concrete of the slab, and this is still

further enhanced by the distributing or anchoring effect of the

longitudinal stringing rods. Thus these longitudinals, besides serving

to hold the U-bars in position, also increase their effectiveness. They

serve a still further purpose as a most convenient support for the slab

bars, compelling them to take the correct position over the supports,

thus automatically ensuring full and proper provision for reversed

stresses. More than that, they act in compression within the middle

half, and assist in tension toward the ends of the span.

Thus, by using U-bars of the type indicated, in combination with

longitudinal bars as described, tying together thoroughly the component

parts of the beam in a vertical plane, a marked increase in stiffness,

if not strength, is secured. This being the case, who can gainsay the

utility of the U-bar?

Of course, near the ends, in case continuity of action is realized,

whereupon the stresses are reversed, the U-bars need to be inverted,

although frequently inversion is not imperative with the type of U-bar

described, the simple hooking of the upper ends over the upper

horizontal steel being sufficient.

As to whether or not the U-bars act with the horizontal and diagonal

steel to form truss systems is relatively unessential; in all

probability there is some such action, which contributes somewhat to the

total strength, but at most it is of minor importance. Mr. Godfrey's

points as to fallacy of truss action seem to be well taken, but his

conclusions in consequence--that U-bars serve no purpose--are

impractical.

The number of U-bars needed is also largely a matter of practice,

although subject to calculation. Practice indicates that they should be

spaced no farther apart than the effective depth of the member, and

spaced closer or made heavier toward the ends, in order to keep pace

with cumulating shear. They need this close spacing in order to serve as

an adequate saddle for the main bars, as well as to furnish, with the

lighter "stringing" rods, an adequate support to the slab bars. They

should have the requisite stiffness in the bends to carry their burden

without appreciable sagging; it will be found that 5/16 in. is about the

minimum practical size, and that 1/2 in. is as large as will be

necessary, even for very deep beams with heavy reinforcement.

If the size and number of U-bars were to be assigned by theory, there

should be enough of them to care for fully 75% of the horizontal shear,

the adhesion of the concrete being assumed as adequate for the

remainder.

Near the ends, of course, the inclined steel, resulting from bending up

some of the horizontal bars, if it is carried well across the support to

secure an adequate anchorage, or other equivalent anchorage is provided,

assists in taking the horizontal shear.

The embedment, too, of large stone in the body of the beam, straddling,

as it were, the neutral plane, and thus forming a lock between the

flange and the stem, may be considered as assisting materially in taking

horizontal shear, thus relieving the U-bars. This is a factor in the

strength of actual work which theory does not take into account, and by

the author, no doubt, it would be regarded as insignificant;

nevertheless it is being done every day, with excellent results.

The action of these various agencies--the U-bars, diagonal steel, and

embedded stone--in a concrete beam, is analogous to that of bolts or

keys in the case of deepened timber beams. A concrete beam may be

assumed, for the purposes of illustration, to be composed of a series of

superimposed layers; in this case the function of the rigid material

crossing these several layers normally, and being well anchored above

and below, as a unifier of the member, is obvious--it acts as so many

bolts joining superimposed planks forming a beam. Of course, no such

lamination actually exists, although there are always incipient forces

tending to produce it; these may and do manifest themselves on occasion

as an actual separation in a horizontal plane at the junction of slab

and stem, ordinarily the plane of greatest weakness--owing to the method

of casting--as well as of maximum horizontal shear. Beams tested to

destruction almost invariably develop cracks in this region. The

question then naturally arises: If U-bars serve no purpose, what will

counteract these horizontal cleaving forces? On the contrary, T-beams,

adequately reinforced with U-bars, seem to be safeguarded in this

respect; consequently, the U-bars, while perhaps adding little to the

strength, as estimated by the ultimate carrying capacity, actually must

be of considerable assistance, within the limit of working loads, by

enhancing the stiffness and ensuring against incipient cracking along

the plane of weakness, such as impact or vibratory loads might induce.

Therefore, U-bars, far from being superfluous or fallacious, are,

practically, if not theoretically, indispensable.

At present there seems to be considerable diversity of opinion as to the

exact nature of the stress action in a reinforced concrete beam.

Unquestionably, the action in the monolithic members of a concrete

structure is different from that in the simple-acting, unrestrained

parts of timber or structural steel construction; because in monolithic

members, by the law of continuity, reverse stresses must come into play.

To offset these stresses reinforcement must be provided, or cracking

will ensue where they occur, to the detriment of the structure in

appearance, if not in utility. Monolithic concrete construction should

be tied together so well across the supports as to make cracking under

working loads impossible, and, when tested to destruction, failure

should occur by the gradual sagging of the member, like the sagging of

an old basket. Then, and then only, can the structure be said to be

adequately reinforced.

In his advocacy of placing steel to simulate a catenary curve, with end

anchorage, the author is more nearly correct than in other issues he

makes. Undoubtedly, an attempt should be made in every concrete

structure to approximate this alignment. In slabs it may be secured

simply by elevating the bars over the supports, when, if pliable enough,

they will assume a natural droop which is practically ideal; or, if too

stiff, they may be bent to conform approximately to this position. In

slabs, too, the reinforcement may be made practically continuous, by

using lengths covering several spans, and, where ends occur, by

generous lapping. In beams the problem is somewhat more complicated,

as it is impossible, except rarely, to bow the steel and to extend it

continuously over several supports; but all or part of the horizontal

steel can be bent up at about the quarter point, carried across the

supports into the adjacent spans, and anchored there by bending it down

at about the same angle as it is bent up on the approach, and then

hooking the ends.

[Illustration: PLATE III.--JUNCTION OF BEAM AND WALL COLUMN.

REINFORCEMENT IN PLACE IN BEAM, LINTEL, AND SLAB UP TO BEAM. NOTE END

ANCHORAGE OF BEAM BARS.]

It is seldom necessary to adopt the scheme proposed by the author,

namely, a threaded end with a bearing washer and a nut to hold the

washer in place, although it is sometimes expedient, but not absolutely

necessary, in end spans, where prolongation into an adjacent span is out

of the question. In end spans it is ordinarily sufficient to give the

bars a double reverse bend, as shown in Plate III, and possibly to clasp

hooks with the horizontal steel. If steel be placed in this manner, the

catenary curve will be practically approximated, the steel will be

fairly developed throughout its length of embedment, and the structure

will be proof against cracking. In this case, also, there is much less

dependence on the integrity of the bond; in fact, if there were no bond,

the structure would still develop most of its strength, although the

deflection under heavy loading might be relatively greater.

The writer once had an experience which sustains this point. On peeling

off the forms from a beam reinforced according to the method indicated,

it was found that, because of the crowding together of the bars in the

bottom, coupled with a little too stiff a mixture, the beam had hardly

any concrete on the underside to grip the steel in the portion between

the points of bending up, or for about the middle half of the member;

consequently, it was decided to test this beam. The actual working load

was first applied and no deflection, cracking, or slippage of the bars

was apparent; but, as the loading was continued, deflection set in and

increased rapidly for small increments of loading, a number of fine

cracks opened up near the mid-section, which extended to the neutral

plane, and the steel slipped just enough, when drawn taut, to destroy

what bond there was originally, owing to the contact of the concrete

above. At three times the live load, or 450 lb. per sq. ft., the

deflection apparently reached a maximum, being about 5/16 in. for a

clear distance, between the supports, of 20 ft.; and, as the load was

increased to 600 lb. per sq. ft., there was no appreciable increase

either in deflection or cracking; whereupon, the owner being satisfied,

the loading was discontinued. The load was reduced in amount to three

times the working load (450 lb.) and left on over night; the next

morning, there being no detectable change, the beam was declared to be

sound. When the load was removed the beam recovered all but about 1/8

in. of its deflection, and then repairs were made by attaching light

expanded metal to the exposed bars and plastering up to form. Although

nearly three years have elapsed, there have been no unfavorable

indications, and the owner, no doubt, has eased his mind entirely in

regard to the matter. This truly remarkable showing can only be

explained by the catenary action of the main steel, and some truss

action by the steel which was horizontal, in conjunction with the

U-bars, of which there were plenty. As before noted, the clear span

was 20 ft., the width of the bay, 8 ft., and the size under the slab

(which was 5 in. thick) 8 by 18 in. The reinforcement consisted of three

1-1/8-in. round medium-steel bars, with 3/8-in. U-bars placed the

effective depth of the member apart and closer toward the supports, the

first two or three being 6 in. apart, the next two or three, 9 in., the

next, 12 in., etc., up to a maximum, throughout the mid-section, of 15

in. Each U-bar was provided with a hook at its upper end, as shown in

Plate III, and engaged the slab reinforcement, which in this case was

expanded metal. Two of the 1-1/8-in. bars were bent up and carried

across the support. At the point of bending up, where they passed the

single horizontal bar, which was superimposed, a lock-bar was inserted,

by which the pressure of the bent-up steel against the concrete, in the

region of the bend, was taken up and distributed along the horizontal

bar. This feature is also shown in Fig. 14. The bars, after being

carried across the support, were inclined into the adjacent span and

provided with a liberal, well-rounded hook, furnishing efficient

anchorage and provision for reverse stresses. This was at one end only,

for--to make matters worse--the other end was a wall bearing;

consequently, the benefit of continuity was denied. The bent-up bars

were given a double reverse bend, as already described, carrying them

around, down, in, and up, and ending finally by clasping them in the

hook of the horizontal bar. This apparently stiffened up the free end,

for, under the test load, its action was similar to that of the

completely restrained end, thus attesting the value of this method of

end-fixing.

The writer has consistently followed this method of reinforcement, with

unvaryingly good results, and believes that, in some measure, it

approximates the truth of the situation. Moreover, it is economical, for

with the bars bent up over the supports in this manner, and positively

anchored, plenty of U-bars being provided, it is possible to remove

the forms with entire safety much sooner than with the ordinary methods

which are not as well stirruped and only partially tied across the

supports. It is also possible to put the structure into use at an

earlier date. Failure, too, by the premature removal of the centers, is

almost impossible with this method. These considerations more than

compensate for the trouble and expense involved in connection with such

reinforcement. The writer will not attempt here a theoretical analysis

of the stresses incurred in the different parts of this beam, although

it might be interesting and instructive.

[Illustration: FIG. 14.]

The concrete, with the reinforcement disposed as described, may be

regarded as reposing on the steel as a saddle, furnishing it with a

rigid jacket in which to work, and itself acting only as a stiff floor

and a protecting envelope. Bond, in this case, while, of course, an

adjunct, is by no means vitally important, as is generally the case with

beams unrestrained in any way and in which the reinforcement is not

provided with adequate end anchorage, in which case a continuous bond is

apparently--at any rate, theoretically--indispensable.

An example of the opposite extreme in reinforced concrete design, where

provision for reverse stresses was almost wholly lacking, is shown in

the Bridgeman Brothers' Building, in Philadelphia, which collapsed while

the operation of casting the roof was in progress, in the summer of

1907. The engineering world is fairly familiar with the details of this

disaster, as they were noted both in the lay and technical press. In

this structure, not only were U-bars almost entirely absent, but the

few main bars which were bent up, were stopped short over the support.

The result was that the ties between the rib and the slab, and also

across the support, being lacking, some of the beams, the forms of which

had been removed prematurely, cracked of their own dead weight, and,

later, when the roof collapsed, owing to the deficient bracing of the

centers, it carried with it each of the four floors to the basement, the

beams giving way abruptly over the supports. Had an adequate tie of

steel been provided across the supports, the collapse, undoubtedly,

would have stopped at the fourth floor. So many faults were apparent in

this structure, that, although only half of it had fallen, it was

ordered to be entirely demolished and reconstructed.

The cracks in the beams, due to the action of the dead weight alone,

were most interesting, and illuminative of the action which takes place

in a concrete beam. They were in every case on the diagonal, at an angle

of approximately 45°, and extended upward and outward from the edge of

the support to the bottom side of the slab. Never was the necessity for

diagonal steel, crossing this plane of weakness, more emphatically

demonstrated. To the writer--an eye-witness--the following line of

thought was suggested:

Should not the concrete in the region above the supports and for a

distance on either side, as encompassed by the opposed 45° lines (Fig.

14), be regarded as abundantly able, of and by itself, and without

reinforcing, to convey all its load into the column, leaving only the

bending to be considered in the truncated portion intersected? Not even

the bending should be considered, except in the case of relatively

shallow members, but simply the tendency on the part of the wedge-shaped

section to slip out on the 45° planes, thereby requiring sufficient

reinforcement at the crossing of these planes of principal weakness to

take the component of the load on this portion, tending to shove it out.

This reinforcement, of course, should be anchored securely both ways; in

mid-span by extending it clear through, forming a suspensory, and, in

the other direction, by prolonging it past the supports, the concrete,

in this case, along these planes, being assumed to assist partly or not

at all.

This would seem to be a fair assumption. In all events, beams designed

in this manner and checked by comparison with the usual methods of

calculation, allowing continuity of action, are found to agree fairly

well. Hence, the following statement seems to be warranted: If enough

steel is provided, crossing normally or nearly so the 45° planes from

the edge of the support upward and outward, to care for the component of

the load on the portion included within a pair of these planes, tending

to produce sliding along the same, and this steel is adequately anchored

both ways, there will be enough reinforcement for every other purpose.

In addition, U-bars should be provided for practical reasons.

The weak point of beams, and slabs also, fully reinforced for continuity

of action, is on the under side adjacent to the edge of the support,

where the concrete is in compression. Here, too, the amount of concrete

available is small, having no slab to assist it, as is the case within

the middle section, where the compression is in the top. Over the

supports, for the width of the column, there is abundant strength, for

here the steel has a leverage equal to the depth of the column; but at

the very edge and for at least one-tenth of the span out, conditions are

serious. The usual method of strengthening this region is to subpose

brackets, suitably proportioned, to increase the available compressive

area to a safe figure, as well as the leverage of the steel, at the same

time diminishing the intensity of compression. Brackets, however, are

frequently objectionable, and are therefore very generally omitted by

careless or ignorant designers, no especial compensation being made for

their absence. In Europe, especially in Germany, engineers are much more

careful in this respect, brackets being nearly always included. True, if

brackets are omitted, some compensation is provided by the strengthening

which horizontal bars may give by extending through this region, but

sufficient additional compressive resistance is rarely afforded thereby.

Perhaps the best way to overcome the difficulty, without resorting to

brackets, is to increase the compressive resistance of the concrete, in

addition to extending horizontal steel through it. This may be done by

hooping or by intermingling scraps of iron or bits of expanded metal

with the concrete, thereby greatly increasing its resistance. The

experiments made by the Department of Bridges of the City of New York,

on the value of nails in concrete, in which results as high as 18,000

lb. per sq. in. were obtained, indicate the availability of this device;

the writer has not used it, nor does he know that it has been used, but

it seems to be entirely rational, and to offer possibilities.

Another practical test, which indicates the value of proper

reinforcement, may be mentioned. In a storage warehouse in Canada, the

floor was designed, according to the building laws of the town, for a

live load of 150 lb. per sq. ft., but the restrictions being more severe

than the standard American practice, limiting the lever arm of the steel

to 75% of the effective depth, this was about equivalent to a 200-lb.

load in the United States. The structure was to be loaded up to 400 or

500 lb. per sq. ft. steadily, but the writer felt so confident of the

excess strength provided by his method of reinforcing that he was

willing to guarantee the structure, designed for 150 lb., according to

the Canadian laws, to be good for the actual working load. Plain, round,

medium-steel bars were used. A 10-ft. panel, with a beam of 14-ft. span,

and a slab 6 in. thick (not including the top coat), with 1/2-in. round

bars, 4 in. on centers, was loaded to 900 lb. per sq. ft., at which load

no measurable deflection was apparent. The writer wished to test it

still further, but there was not enough cement--the material used for

loading. The load, however, was left on for 48 hours, after which, no

sign of deflection appearing, not even an incipient crack, it was

removed. The total area of loading was 14 by 20 ft. The beam was

continuous at one end only, and the slab only on one side. In other

parts of the structure conditions were better, square panels being

possible, with reinforcement both ways, and with continuity, both of

beams and slabs, virtually in every direction, end spans being

compensated by shortening. The method of reinforcing was as before

indicated. The enormous strength of the structure, as proved by this

test, and as further demonstrated by its use for nearly two years, can

only be explained on the basis of the continuity of action developed and

the great stiffness secured by liberal stirruping. Steel was provided in

the middle section according to the rule, (_w_ _l_)/8, the span being

taken as the clear distance between the supports; two-thirds of the

steel was bent up and carried across the supports, in the case of the

beams, and three-fourths of the slab steel was elevated; this, with the

lap, really gave, on the average, four-thirds as much steel over the

supports as in the center, which, of course, was excessive, but usually

an excess has to be tolerated in order to allow for adequate anchorage.

Brackets were not used, but extra horizontal reinforcement, in addition

to the regular horizontal steel, was laid in the bottom across the

supports, which, seemingly, was satisfactory. The columns, it should be

added, were calculated for a very low value, something like 350 lb. per

sq. in., in order to compensate for the excess of actual live load over

and above the calculated load.

This piece of work was done during the winter, with the temperature

almost constantly at +10° and dropping below zero over night. The

precautions observed were to heat the sand and water, thaw out the

concrete with live steam, if it froze in transporting or before it

was settled in place, and as soon as it was placed, it was decked

over and salamanders were started underneath. Thus, a job equal in every

respect to warm-weather installation was obtained, it being possible to

remove the forms in a fortnight.

[Illustration: PLATE IV, FIG. 1.--SLAB AND BEAM REINFORCEMENT

CONTINUOUS OVER SUPPORTS. SPAN OF BEAMS = 14 FT. SPAN OF SLABS = 12 FT.

SLAB, 6 IN. THICK.]

[Illustration: PLATE IV, FIG. 2.--REINFORCEMENT IN PLACE OVER ONE

COMPLETE FLOOR OF STORAGE WAREHOUSE. SLABS, 14 FT. SQUARE. REINFORCED

TWO WAYS. NOTE CONTINUITY OF REINFORCEMENT AND ELEVATION OVER SUPPORTS.

FLOOR DESIGNED FOR 150 LB. PER SQ. FT. LIVE LOAD. TESTED TO 900 LB. PER

SQ. FT.]

In another part of this job (the factory annex) where, owing to the open

nature of the structure, it was impossible to house it in as well as the

warehouse which had bearing walls to curtain off the sides, less

fortunate results were obtained. A temperature drop over night of nearly

50°, followed by a spell of alternate freezing and thawing, effected the

ruin of at least the upper 2 in. of a 6-in. slab spanning 12 ft. (which

was reinforced with 1/2-in. round bars, 4 in. on centers), and the

remaining 4 in. was by no means of the best quality. It was thought that

this particular bay would have to be replaced. Before deciding, however,

a test was arranged, supports being provided underneath to prevent

absolute failure. But as the load was piled up, to the extent of nearly

400 lb. per sq. ft., there was no sign of giving (over this span) other

than an insignificant deflection of less than 1/4 in., which disappeared

on removing the load. This slab still performs its share of the duty,

without visible defect, hence it must be safe. The question naturally

arises: if 4 in. of inferior concrete could make this showing, what must

have been the value of the 6 in. of good concrete in the other slabs?

The reinforcing in the slab, it should be stated, was continuous over

several supports, was proportioned for (_w_ _l_)/8 for the clear span

(about 11 ft.), and three-fourths of it was raised over the supports.

This shows the value of the continuous method of reinforcing, and the

enormous excess of strength in concrete structures, as proportioned by

existing methods, when the reverse stresses are provided for fully and

properly, though building codes may make no concession therefor.

Another point may be raised, although the author has not mentioned it,

namely, the absurdity of the stresses commonly considered as occurring

in tensile steel, 16,000 lb. per sq. in. for medium steel being used

almost everywhere, while some zealots, using steel with a high elastic

limit, are advocating stresses up to 22,000 lb. and more; even the

National Association of Cement Users has adopted a report of the

Committee on Reinforced Concrete, which includes a clause recommending

the use of 20,000 lb. on high steel. As theory indicates, and as F.E.

Turneaure, Assoc. M. Am. Soc. C. E., of the University of Wisconsin, has

proven by experiment, failure of the concrete encircling the steel under

tension occurs when the stress in the steel is about 5,000 lb. per sq.

in. It is evident, therefore, that if a stress of even 16,000 lb. were

actually developed, not to speak of 20,000 lb. or more, the concrete

would be so replete with minute cracks on the tension side as to expose

the embedded metal in innumerable places. Such cracks do not occur in

work because, under ordinary working loads, the concrete is able to

carry the load so well, by arch and dome action, as to require very

little assistance from the steel, which, consequently, is never stressed

to a point where cracking of the concrete will be induced. This being

the case, why not recognize it, modify methods of design, and not go on

assuming stresses which have no real existence?

The point made by Mr. Godfrey in regard to the fallacy of sharp bends is

patent, and must meet with the agreement of all who pause to think of

the action really occurring. This is also true of his points as to the

width of the stem of T-beams, and the spacing of bars in the same. As to

elastic arches, the writer is not sufficiently versed in designs of this

class to express an opinion, but he agrees entirely with the author in

his criticism of retaining-wall design. What the author proposes is

rational, and it is hard to see how the problem could logically be

analyzed otherwise. His point about chimneys, however, is not as clear.

As to columns, the writer agrees with Mr. Godfrey in many, but not in

all, of his points. Certainly, the fallacy of counting on vertical steel

to carry load, in addition to the concrete, has been abundantly shown.

The writer believes that the sole legitimate function of vertical steel,

as ordinarily used, is to reinforce the member against flexure, and that

its very presence in the column, unless well tied across by loops of

steel at frequent intervals, so far from increasing the direct carrying

capacity, is a source of weakness. However, the case is different when a

large amount of rigid vertical steel is used; then the steel may be

assumed to carry all the load, at the value customary in structural

steel practice, the concrete being considered only in the light of

fire-proofing and as affording lateral support to the steel, increasing

its effective radius of gyration and thus its safe carrying capacity. In

any event the load should be assumed to be carried either by the

concrete or by the steel, and, if by the former, the longitudinal and

transverse steel which is introduced should be regarded as auxiliary

only. Vertical steel, if not counted in the strength, however, may on

occasion serve a very useful practical purpose; for instance, the writer

once had a job where, owing to the collection of ice and snow on a

floor, which melted when the salamanders were started, the lower ends of

several of the superimposed columns were eaten away, with the result

that when the forms were withdrawn, these columns were found to be

standing on stilts. Only four 1-in. bars were present, looped at

intervals of about 1 ft., in a column 12 ft. in length and having a

girth of 14 in., yet they were adequate to carry both the load of the

floor above and the load incidental to construction. If no such

reinforcement had been provided, however, failure would have been

inevitable. Thus, again, it is shown that, where theory and experiment

may fail to justify certain practices, actual experience does, and

emphatically.

Mr. Godfrey is absolutely right in his indictment of hooping as usually

done, for hoops can serve no purpose until the concrete contained

therein is stressed to incipient rupture; then they will begin to act,

to furnish restraint which will postpone ultimate failure. Mr. Godfrey

states that, in his opinion, the lamina of concrete between each hoop is

not assisted; but, as a matter of fact, practically regarded, it is, the

coarse particles of the aggregate bridging across from hoop to hoop; and

if--as is the practice of some--considerable longitudinal steel is also

used, and the hoops are very heavy, so that when the bridging action of

the concrete is taken into account, there is in effect a very

considerable restraining of the concrete core, and the safe carrying

capacity of the column is undoubtedly increased. However, in the latter

case, it would be more logical to consider that the vertical steel

carried all the load, and that the concrete core, with the hoops, simply

constituted its rigidity and the medium of getting the load into the

same, ignoring, in this event, the direct resistance of the concrete.

What seems to the writer to be the most logical method of reinforcing

concrete columns remains to be developed; it follows along the lines of

supplying tensile resistance to the mass here and there throughout, thus

creating a condition of homogeneity of strength. It is precisely the

method indicated by the experiments already noted, made by the

Department of Bridges of the City of New York, whereby the compressive

resistance of concrete was enormously increased by intermingling wire

nails with it. Of course, it is manifestly out of the question,

practically and economically, to reinforce column concrete in this

manner, but no doubt a practical and an economical method will be

developed which will serve the same purpose. The writer knows of one

prominent reinforced concrete engineer, of acknowledged judgment, who

has applied for a patent in which expanded metal is used to effect this

very purpose; how well this method will succeed remains to be seen. At

any rate, reinforcement of this description seems to be entirely

rational, which is more than can be said for most of the current

standard types.

Mr. Godfrey's sixteenth point, as to the action in square panels, seems

also to the writer to be well taken; he recollects analyzing Mr.

Godfrey's narrow-strip method at the time it appeared in print, and

found it rational, and he has since had the pleasure of observing actual

tests which sustained this view. Reinforcement can only be efficient in

two ways, if the span both ways is the same or nearly so; a very little

difference tends to throw the bulk of the load the short way, for

stresses know only one law, namely, to follow the shortest line. In

square panels the maximum bending comes on the mid-strips; those

adjacent to the margin beams have very little bending parallel to the

beam, practically all the action being the other way; and there are all

gradations between. The reinforcing, therefore, should be spaced the

minimum distance only in the mid-region, and from there on constantly

widened, until, at about the quarter point, practically none is

necessary, the slab arching across on the diagonal from beam to beam.

The practice of spacing the bars at the minimum distance throughout is

common, extending the bars to the very edge of the beams. In this case

about half the steel is simply wasted.

In conclusion, the writer wishes to thank Mr. Godfrey for his very able

paper, which to him has been exceedingly illuminative and fully

appreciated, even though he has been obliged to differ from its

contentions in some respects. On the other hand, perhaps, the writer is

wrong and Mr. Godfrey right; in any event, if, through the medium of

this contribution to the discussion, the writer has assisted in

emphasizing a few of the fundamental truths; or if, in his points of

non-concordance, he is in coincidence with the views of a sufficient

number of engineers to convince Mr. Godfrey of any mistaken stands; or,

finally, if he has added anything new to the discussion which may help

along the solution, he will feel amply repaid for his time and labor.

The least that can be said is that reform all along the line, in matters

of reinforced concrete design, is insistent.

JOHN STEPHEN SEWELL, M. AM. SOC. C. E. (by letter).--The author is

rather severe on the state of the art of designing reinforced concrete.

It appears to the writer that, to a part of the indictment, at least, a

plea of not guilty may properly be entered; and that some of the other

charges may not be crimes, after all. There is still room for a wide

difference of opinion on many points involved in the design of

reinforced concrete, and too much zeal for conviction, combined with

such skill in special pleading as this paper exhibits, may possibly

serve to obscure the truth, rather than to bring it out clearly.

_Point 1._--This is one to which the proper plea is "not guilty." The

writer does not remember ever to have seen just the type of construction

shown in Fig. 1, either used or recommended. The angle at which the bars

are bent up is rarely as great as 45°, much less 60 degrees. The writer

has never heard of "sharp bends" being insisted on, and has never seen

them used; it is simply recommended or required that some of the bars be

bent up and, in practice, the bend is always a gentle one. The stress to

be carried by the concrete as a queen-post is never as great as that

assumed by the author, and, in practice, the queen-post has a much

greater bearing on the bars than is indicated in Fig. 1.

_Point 2._--The writer, in a rather extensive experience, has never seen

this point exemplified.

_Point 3._--It is probable that as far as Point 3 relates to retaining

walls, it touches a weak spot sometimes seen in actual practice, but

necessity for adequate anchorage is discussed at great length in

accepted literature, and the fault should be charged to the individual

designer, for correct information has been within his reach for at least

ten years.

_Point 4._--In this case it would seem that the author has put a wrong

interpretation on what is generally meant by shear. However, it is

undoubtedly true that actual shear in reinforcing steel is sometimes

figured and relied on. Under some conditions it is good practice, and

under others it is not. Transverse rods, properly placed, can surely act

in transmitting stress from the stem to the flange of a T-beam, and

could properly be so used. There are other conditions under which the

concrete may hold the rods so rigidly that their shearing strength may

be utilized; where such conditions do not obtain, it is not ordinarily

necessary to count on the shearing strength of the rods.

_Point 5._--Even if vertical stirrups do not act until the concrete has

cracked, they are still desirable, as insuring a gradual failure and,

generally, greater ultimate carrying capacity. It would seem that the

point where their full strength should be developed is rather at the

neutral axis than at the centroid of compression stresses. As they are

usually quite light, this generally enables them to secure the requisite

anchorage in the compressed part of the concrete. Applied to a riveted

truss, the author's reasoning would require that all the rivets by which

web members are attached to the top chord should be above the center of

gravity of the chord section.

_Point 6._--There are many engineers who, accepting the common theory of

diagonal tension and compression in a solid beam, believe that, in a

reinforced concrete beam with stirrups, the concrete can carry the

diagonal compression, and the stirrups the tension. If these web

stresses are adequately cared for, shear can be neglected.

The writer cannot escape the conclusion that tests which have been made

support the above belief. He believes that stirrups should be inclined

at an angle of 45° or less, and that they should be fastened rigidly to

the horizontal bars; but that is merely the most efficient way to use

them--not the only way to secure the desired action, at least, in some

degree.

The author's proposed method of bending up some of the main bars is

good, but he should not overlook the fact that he is taking them away

from the bottom of the beam just as surely as in the case of a sharp

bend, and this is one of his objections to the ordinary method of

bending them up. Moreover, with long spans and varying distances of the

load, the curve which he adopts for his bars cannot possibly be always

the true equilibrium curve. His concrete must then act as a stiffening

truss, and will almost inevitably crack before his cable can come into

action as such.

Bulletin No. 29 of the University of Illinois contains nothing to

indicate that the bars bent up in the tests reported were bent up in any

other than the ordinary way; certainly they could not be considered as

equivalent to the cables of a suspension bridge. These beams behaved

pretty well, but the loads were applied so as to make them practically

queen-post trusses, symmetrically loaded. While the bends in the bars

were apparently not very sharp, and the angle of inclination was much

less than 60°, or even 45°, it is not easy to find adequate bearings for

the concrete posts on theoretical grounds, yet it is evident that the

bearing was there just the same. The last four beams of the series,

521-1, 521-2, 521-5, 521-6, were about as nearly like Fig. 1 as anything

the writer has ever seen in actual practice, yet they seem to have been

the best of all. To be sure, the ends of the bent-up bars had a rather

better anchorage, but they seem to have managed the shear question

pretty much according to the expectation of their designer, and it is

almost certain that the latter's assumptions would come under some part

of the author's general indictment. These beams would seem to justify

the art in certain practices condemned by the author. Perhaps he

overlooked them.

_Point 7._--The writer does not believe that the "general" practice as

to continuity is on the basis charged. In fact, the general practice

seems to him to be rather in the reverse direction. Personally, the

writer believes in accepting continuity and designing for it, with

moments at both center and supports equal to two-thirds of the center

movement for a single span, uniformly loaded. He believes that the

design of reinforced concrete should not be placed on the same footing

as that of structural steel, because there is a fundamental difference,

calling for different treatment. The basis should be sound, in both

cases; but what is sound for one is not necessarily so for the other. In

the author's plan for a series of spans designed as simple beams, with a

reasonable amount of top reinforcement, he might get excessive stress

and cracks in the concrete entirely outside of the supports. The shear

would then become a serious matter, but no doubt the direct

reinforcement would come into play as a suspension bridge, with further

cracking of the concrete as a necessary preliminary.

Unfortunately, the writer is unable to refer to records, but he is quite

sure that, in the early days, the rivets and bolts in the upper part of

steel and iron bridge stringer connections gave some trouble by failing

in tension due to continuous action, where the stringers were of

moderate depth compared to the span. Possibly some members of the

Society may know of such instances. The writer's instructors in

structural design warned him against shallow stringers on that account,

and told him that such things had happened.

Is it certain that structural steel design is on such a sound basis

after all? Recent experiences seem to cast some doubt on it, and we may

yet discover that we have escaped trouble, especially in buildings,

because we almost invariably provide for loads much greater than are

ever actually applied, and not because our knowledge and practice are

especially exact.

_Point 8._--The writer believes that this point is well taken, as to a

great deal of current practice; but, if the author's ideas are carried

out, reinforced concrete will be limited to a narrow field of

usefulness, because of weight and cost. With attached web members, the

writer believes that steel can be concentrated in heavy members in a way

that is not safe with plain bars, and that, in this way, much greater

latitude of design may be safely allowed.

_Point 9._--The writer is largely in accord with the author's ideas on

the subject of T-beams, but thinks he must have overlooked a very

careful and able analysis of this kind of member, made by A.L. Johnson,

M. Am. Soc. C. E., a number of years ago. While too much of the floor

slab is still counted on for flange duty, it seems to the writer that,

within the last few years, practice has greatly improved in this

respect.

_Point 10._--The author's statement regarding the beam and slab formulas

in common use is well grounded. The modulus of elasticity of concrete is

so variable that any formulas containing it and pretending to determine

the stress in the concrete are unreliable, but the author's proposed

method is equally so. We can determine by experiment limiting

percentages of steel which a concrete of given quality can safely carry

as reinforcement, and then use empirical formulas based on the stress in

the steel and an assumed percentage of its depth in the concrete as a

lever arm with more ease and just as much accuracy. The common methods

result in designs which are safe enough, but they pretend to determine

the stress in concrete; the writer does not believe that that is

possible within 30% of the truth, and can see no profit in making

laborious calculations leading to such unreliable results.

_Point 11._--The writer has never designed a reinforced concrete

chimney, but if he ever has to do so, he will surely not use any formula

that is dependent on the modulus of elasticity of concrete.

_Points 12, 13, and 14._--The writer has never had to consider these

points to any extent in his own work, and will leave discussion to those

better qualified.

_Point 15._--There is much questionable practice in regard to reinforced

concrete columns; but the matter is hardly disposed of as easily as

indicated by the author. Other engineers draw different conclusions from

the tests cited by the author, and from some to which he does not refer.

To the writer it appears that here is a problem still awaiting solution

on a really satisfactory basis. It seems incredible that the author

would use plain concrete in columns, yet that seems to be the inference.

The tests seem to indicate that there is much merit in both hooping and

longitudinal reinforcement, if properly designed; that the

fire-resisting covering should not be integral with the columns proper;

that the high results obtained by M. Considère in testing small

specimens cannot be depended on in practice, but that the reinforcement

is of great value, nevertheless. The writer believes that when

load-carrying capacity, stresses due to eccentricity, and fire-resisting

qualities are all given due consideration, a type of column with close

hooping and longitudinal reinforcement provided with shear members, will

finally be developed, which will more than justify itself.

_Point 16_.--The writer has not gone as deeply into this question, from

a theoretical point of view, as he would like; but he has had one

experience that is pertinent. Some years ago, he built a plain slab

floor supported by brick walls. The span was about 16 ft. The dimensions

of the slab at right angles to the reinforcement was 100 ft. or more.

Plain round bars, 1/2 in. in diameter, were run at right angles to the

reinforcement about 2 ft. on centers, the object being to lessen cracks.

The reinforcement consisted of Kahn bars, reaching from wall to wall.

The rounds were laid on top of the Kahn bars. The concrete was frozen

and undeniably damaged, but the floors stood up, without noticeable

deflection, after the removal of the forms. The concrete was so soft,

however, that a test was decided on. An area about 4 ft. wide, and

extending to within about 1 ft. of each bearing wall, was loaded with

bricks piled in small piers not in contact with each other, so as to

constitute practically a uniformly distributed load. When the total load

amounted to much less than the desired working load for the 4-ft. strip,

considerable deflection had developed. As the load increased, the

deflection increased, and extended for probably 15 or 20 ft. on either

side of the loaded area. Finally, under about three-fourths of the

desired breaking load for the 4-ft. strip, it became evident that

collapse would soon occur. The load was left undisturbed and, in 3 or 4

min., an area about 16 ft. square tore loose from the remainder of the

floor and fell. The first noticeable deflection in the above test

extended for 8 or 10 ft. on either side of the loaded strip. It would

seem that this test indicated considerable distributing power in the

round rods, although they were not counted as reinforcement for

load-carrying purposes at all. The concrete was extremely poor, and none

of the steel was stressed beyond the elastic limit. While this test may

not justify the designer in using lighter reinforcement for the short

way of the slab, it at least indicates a very real value for some

reinforcement in the other direction. It would seem to indicate, also,

that light steel members in a concrete slab might resist a small amount

of shear. The slab in this case was about 6 in. thick.

SANFORD E. THOMPSON, M. AM. SOC. C. E. (by letter).--Mr. Godfrey's

sweeping condemnation of reinforced concrete columns, referred to in his

fifteenth point, should not be passed over without serious criticism.

The columns in a building, as he states, are the most vital portion of

the structure, and for this very reason their design should be governed

by theoretical and practical considerations based on the most

comprehensive tests available.

The quotation by Mr. Godfrey from a writer on hooped columns is

certainly more radical than is endorsed by conservative engineers, but

the best practice in column reinforcement, as recommended by the Joint

Committee on Concrete and Reinforced Concrete, which assumes that the

longitudinal bars assist in taking stress in accordance with the ratio

of elasticity of steel to concrete, and that the hooping serves to

increase the toughness of the column, is founded on the most substantial

basis of theory and test.

In preparing the second edition of "Concrete, Plain and Reinforced," the

writer examined critically the various tests of concrete columns in

order to establish a definite basis for his conclusions. Referring more

particularly to columns reinforced with vertical steel bars, an

examination of all the tests of full-sized columns made in the United

States appears to bear out the fact very clearly that longitudinal steel

bars embedded in concrete increase the strength of the column, and,

further, to confirm the theory by which the strength of the combination

of steel and concrete may be computed and is computed in practice.

Tests of large columns have been made at the Watertown Arsenal, the

Massachusetts Institute of Technology, the University of Illinois, by

the City of Minneapolis, and at the University of Wisconsin. The results

of these various tests were recently summarized by the writer in a paper

presented at the January, 1910, meeting of the National Association of

Cement Users[O]. Reference may be made to this paper for fuller

particulars, but the averages of the tests of each series are worth

repeating here.

In comparing the averages of reinforced columns, specimens with spiral

or other hooping designed to increase the strength, or with horizontal

reinforcement placed so closely together as to prevent proper placing of

the concrete, are omitted. For the Watertown Arsenal tests the averages

given are made up from fair representative tests on selected proportions

of concrete, given in detail in the paper referred to, while in other

cases all the corresponding specimens of the two types are averaged. The

results are given in Table 1.

The comparison of these tests must be made, of course, independently in

each series, because the materials and proportions of the concrete and

the amounts of reinforcement are different in the different series. The

averages are given simply to bring out the point, very definitely and

distinctly, that longitudinally reinforced columns are stronger than

columns of plain concrete.

A more careful analysis of the tests shows that the reinforced columns

are not only stronger, but that the increase in strength due to the

reinforcement averages greater than the ordinary theory, using a ratio

of elasticity of 15, would predicate.

Certain of the results given are diametrically opposed to Mr. Godfrey's

conclusions from the same sets of tests. Reference is made by him, for

example (page 69), to a plain column tested at the University of

Illinois, which crushed at 2,001 lb. per sq. in., while a reinforced

column of similar size crushed at 1,557 lb. per sq. in.,[P] and the

author suggests that "This is not an isolated case, but appears to be

the rule." Examination of this series of tests shows that it is somewhat

more erratic than most of those made at the University of Illinois, but,

even from the table referred to by Mr. Godfrey, pursuing his method of

reasoning, the reverse conclusion might be reached, for if, instead of

selecting, as he has done, the weakest reinforced column in the entire

lot and the strongest plain column, a reverse selection had been made,

the strength of the plain column would have been stated as 1,079 lb. per

sq. in. and that of the reinforced column as 3,335 lb. per sq. in. If

extremes are to be selected at all, the weakest reinforced column should

be compared with the weakest plain column, and the strongest reinforced

column with the strongest plain column; and the results would show that

while an occasional reinforced column may be low in strength, an

occasional plain column will be still lower, so that the reinforcement,

even by this comparison, is of marked advantage in increasing strength.

In such cases, however, comparisons should be made by averages. The

average strength of the reinforced columns, even in this series, as

given in Table 1, is considerably higher than that of the plain columns.

TABLE 1.--AVERAGE RESULTS OF TESTS OF PLAIN _vs._

LONGITUDINALLY REINFORCED COLUMNS.

--------------+--------+--------------+---------------------------------

| | Average |

|Average | strength of |

Location |strength|longitudinally| Reference.

of test. |of plain| reinforced |

|columns.| columns. |

--------------+--------+--------------+---------------------------------

Watertown | 1,781 | 2,992 |Taylor and Thompson's

Arsenal. | | |"Concrete, Plain and Reinforced"

| | |(2nd edition), p. 493.

--------------+--------+--------------+---------------------------------

Massachusetts| 1,750 | 2,370 |_Transactions_,

Institute of | | |Am. Soc. C. E., Vol. L, p. 487.

Technology. | | |

--------------+--------+--------------+---------------------------------

University of| 1,550 | 1,750 |_Bulletin No. 10._

Illinois. | | |University of Illinois, 1907.

--------------+--------+--------------+---------------------------------

City of | 2,020 | 2,300 |_Engineering News_,

Minneapolis.| | |Dec. 3d, 1908, p. 608.

--------------+--------+--------------+---------------------------------

University of| 2,033 | 2,438 |_Proceedings_,

Wisconsin. | | |Am. Soc. for Testing Materials,

| | |Vol. IX, 1909, p. 477.

--------------+--------+--------------+---------------------------------

In referring, in the next paragraph, to Mr. Withey's tests at the

University of Wisconsin, Mr. Godfrey selects for his comparison two

groups of concrete which are not comparable. Mr. Withey, in the paper

describing the tests, refers to two groups of plain concrete columns,

_A1_ to _A4_, and _W1_ to _W3_. He speaks of the uniformity in the tests

of the former group, the maximum variation in the four specimens being

only 2%, but states, with reference to columns, _W1_ to _W3_, that:

"As these 3 columns were made of a concrete much superior to that

in any of the other columns made from 1:2:4 or 1:2:3-1/2 mix, they

cannot satisfactorily be compared with them. Failures of all plain

columns were sudden and without any warning."

Now, Mr. Godfrey, instead of taking columns _A1_ to _A3_, selects for

his comparison _W1_ to _W3_, made, as Mr. Withey distinctly states, with

an especially superior concrete. Taking columns, _A1_ to _A3_, for

comparison with the reinforced columns, _E1_ to _E3_, the result shows

an average of 2,033 for the plain columns and 2,438 for the reinforced

columns.

Again, taking the third series of tests referred to by Mr. Godfrey,

those at Minneapolis, Minn., it is to be noticed that he selects for his

criticism a column which has this note as to the manner of failure:

"Bending at center (bad batch of concrete at this point)." Furthermore,

the column is only 9 by 9 in., and square, and the stress referred to is

calculated on the full section of the column instead of on the strength

within the hooping, although the latter method is the general practice

in a hooped column. The inaccuracy of this is shown by the fact that,

with this small size of square column, more than half the area is

outside the hooping and never taken into account in theoretical

computations. A fair comparison, as far as longitudinal reinforcement is

concerned, is always between the two plain columns and the six columns,

_E_, _D_, and _F_. The results are so instructive that a letter[Q] by

the writer is quoted in full as follows:

"SIR:--

"In view of the fact that the column tests at Minneapolis, as

reported in your paper of December 3, 1908, p. 608, are liable

because of the small size of the specimens to lead to divergent

conclusions, a few remarks with reference to them may not be out of

place at this time.

"1. It is evident that the columns were all smaller, being only 9

in. square, than is considered good practice in practical

construction, because of the difficulty of properly placing the

concrete around the reinforcement.

"2. The tests of columns with flat bands, _A_, _B_, and _C_, in

comparison with the columns _E_, _D_ and _F_, indicate that the

wide bands affected the placing of the concrete, separating the

internal core from the outside shell so that it would have been

nearly as accurate to base the strength upon the material within

the bands, that is, upon a section of 38 sq. in., instead of upon

the total area of 81 sq. in. This set of tests, _A_, _B_ and _C_,

is therefore inconclusive except as showing the practical

difficulty in the use of bands in small columns, and the necessity

for disregarding all concrete outside of the bands when computing

the strength.

"3. The six columns _E_, _D_ and _F_, each of which contained eight

5/8-in. rods, are the only ones which are a fair test of columns

longitudinally reinforced, since they are the only specimens except

the plain columns in which the small sectional area was not cut by

bands or hoops. Taking these columns, we find an average strength

38% in excess of the plain columns, whereas, with the percentage of

reinforcement used, the ordinary formula for vertical steel (using

a ratio of elasticity of steel to concrete of 15) gives 34% as the

increase which might be expected. In other words, the actual

strength of this set of columns was in excess of the theoretical

strength. The wire bands on these columns could not be considered

even by the advocates of hooped columns as appreciably adding to

the strength, because they were square instead of circular. It may

be noted further in connection with these longitudinally reinforced

columns that the results were very uniform and, further, that the

strength of _every specimen_ was much greater than the strength of

the plain columns, being in every case except one at least 40%

greater. In these columns the rods buckled between the bands, but

they evidently did not do so until their elastic limit was passed,

at which time of course they would be expected to fail.

"4. With reference to columns, _A_, _B_, _C_ and _L_, which were

essentially hooped columns, the failure appears to have been caused

by the greater deformation which is always found in hooped columns,

and which in the earlier stages of the loading is apparently due to

lack of homogeneity caused by the difficulty in placing the

concrete around the hooping, and in the later stage of the loading

to the excessive expansion of the concrete. This greater

deformation in a hooped column causes any vertical steel to pass

its elastic limit at an earlier stage than in a column where the

deformation is less, and therefore produces the buckling between

the bands which is noted in these two sets of columns. This

excessive deformation is a strong argument against the use of high

working stresses in hooped columns.

"In conclusion, then, it may be said that the columns reinforced

with vertical round rods showed all the strength that would be

expected of them by theoretical computation. The hooped columns, on

the other hand, that is, the columns reinforced with circular bands

and hoops, gave in all cases comparatively low results, but no

conclusions can be drawn from them because the unit-strength would

have been greatly increased if the columns had been larger so that

the relative area of the internal core to the total area of the

column had been greater."

From this letter, it will be seen that every one of Mr. Godfrey's

comparisons of plain _versus_ reinforced columns requires explanations

which decidedly reduce, if they do not entirely destroy, the force of

his criticism.

This discussion can scarcely be considered complete without brief

reference to the theory of longitudinal steel reinforcement for columns.

The principle[R] is comparatively simple. When a load is placed on a

column of any material it is shortened in proportion, within working

limits, to the load placed upon it; that is, with a column of

homogeneous material, if the load is doubled, the amount of shortening

or deformation is also doubled. If vertical steel bars are embedded in

concrete, they must shorten when the load is applied, and consequently

relieve the concrete of a portion of its load. It is therefore

physically impossible to prevent such vertical steel from taking a

portion of the load unless the steel slips or buckles.

As to the possible danger of the bars in the concrete slipping or

buckling, to which Mr. Godfrey also refers, again must tests be cited.

If the ends are securely held--and this is always the case when bars are

properly butted or are lapped for a sufficient length--they cannot slip.

With reference to buckling, tests have proved conclusively that vertical

bars such as are used in columns, when embedded in concrete, will not

buckle until the elastic limit of the steel is reached, or until the

concrete actually crushes. Beyond these points, of course, neither steel

nor concrete nor any other material is expected to do service.

As proof of this statement, it will be seen, by reference to tests at

the Watertown Arsenal, as recorded in "Tests of Metals," that many of

the columns were made with vertical bar reinforcement having absolutely

no hoops or horizontal steel placed around them. That is, the bars, 8

ft. long, were placed in the four corners of the column--in some tests

only 2 in. from the surface--and held in place simply by the concrete

itself.[S] There was no sign whatever of buckling until the compression

was so great that the elastic limit of the steel was passed, when, of

course, no further strength could be expected from it.

To recapitulate the conclusions reached as a result of a study of the

tests: It is evident that, not only does theory permit the use of

longitudinal bar reinforcement for increasing the strength of concrete

columns, whenever such reinforcement is considered advisable, but that

all the important series of column tests made in the United States to

date show a decisive increase in strength of columns reinforced with

longitudinal steel bars over those which are not reinforced.

Furthermore, as has already been mentioned, without treating the details

of the proof, it can be shown that the tests bear out conclusively the

conservatism of computing the value of the vertical steel bars in

compression by the ordinary formulas based on the ratio of the moduli of

elasticity of steel to concrete.

EDWARD GODFREY, M. AM. SOC. C. E. (by letter).--As was to be expected,

this paper has brought out discussion, some of which is favorable and

flattering; some is in the nature of dust-throwing to obscure the force

of the points made; some would attempt to belittle the importance of

these points; and some simply brings out the old and over-worked

argument which can be paraphrased about as follows: "The structures

stand up and perform their duty, is this not enough?"

Some Mooted Questions in Reinforced Concrete Design American Society of Civil Engineers, Transactions, Paper No. 1169, Volume LXX, Dec. 1910 · 第 13 / 15 题