CHAPTER I.

Transcriber's Notes:

Text printed in italics, bold face and small capitals in the original

work have been transcribed between _underscores_, =equal signs= and

ALL CAPITALS, respectively.

Depending on the hard- and software used to read this text and their

settings, not all characters may display as intended.

More Transcriber's Notes may be found at the end of this text.

Books by

Horstmann & Tousley

Motion Picture Operation, Stage Electrics and Illusions. $2.00

(Ready July 1, 1914.)

Alternating Current Theory, Practice and Diagrams. $2.00

Modern Electric Illumination. $2.00

Practical Armature and Magnet Winding. $1.50

Modern Electrical Construction. $1.50

Electrical Wiring and Construction Tables. $1.50

Dynamo Tending for Engineers. $1.50

Modern Wiring Diagrams and Descriptions. $1.50

Electricians’ Operating and Testing Manual. $1.50

Motion Picture Operation

STAGE ELECTRICS

AND ILLUSIONS

A Practical Hand-book and Guide for Theater

Electricians, Motion Picture Operators and

Managers of Theaters and

Productions

By

Henry C. Horstmann

and

Victor H. Tousley

Authors of

“Alternating Current,” “Modern Wiring Diagrams,” “Modern

Electrical Construction,” “Electrical Wiring and Construction

Tables,” “Practical Armature and Magnet

Winding,” “Electricians’ Operating and Testing

Manual,” “Modern Illumination.”

ILLUSTRATED

[Illustration]

Chicago

FREDERICK J. DRAKE & CO.

Publishers

Copyright 1914, by

HENRY C. HORSTMANN

and

VICTOR H. TOUSLEY

PREFACE

In this volume the authors have attempted to lay before the

Motion-Picture Operators and Theatrical Employes generally, a reference

and handbook making a specialty of electrical requirements about

theaters.

A working knowledge of electricity in general is assumed, and therefore

elementary ideas have been treated sparingly. A specialty, however, has

been made of all matters peculiar to theaters, and it is thought that

theater electricians will find in this volume everything that they need

whether they be operating motion-picture machines or switchboards in

first-class houses.

The two special chapters “Portable Stage Equipment” and “Theater Wiring”

have been arranged so that they are particularly valuable for reference.

They should be consulted before undertaking any electrical construction

work, either for the stage or for the auditorium. These chapters embody

all of the practical knowledge that has come to the notice of the

authors in many years of actual experience with theatrical construction.

The aim of this volume has been to present in a simple and practical way

the essential principles of Motion-Picture Work.

THE AUTHORS.

Table of Contents

PAGE

CHAPTER I

The Electrical Circuit and Electrical Hazards 9

CHAPTER II

The Arc Lamp 19

CHAPTER III

Projection 31

CHAPTER IV

Motion Pictures 55

CHAPTER V

The Motion-Picture Machine 62

CHAPTER VI

The Film 89

CHAPTER VII

General Hints on Installation, Operation and Care of Machines 96

CHAPTER VIII

Light 113

CHAPTER IX

Principles of Vision 122

CHAPTER X

Reflection 126

CHAPTER XI

Refraction 137

CHAPTER XII

Optical Instruments 147

CHAPTER XIII

Optical Illusions 155

CHAPTER XIV

Theater Buildings 163

CHAPTER XV

Operating Room Equipment 176

CHAPTER XVI

Current Control for Arc Lamps 190

CHAPTER XVII

Management of Generators and Motors 213

CHAPTER XVIII

Theater Wiring 218

CHAPTER XIX

Portable Stage Equipment 311

CHAPTER XX

Useful Facts and Formulas 353

CHAPTER XXI

Glossary of Electrical, Mechanical and Optical Words, Terms and

Phrases 358

Index 385

MOTION PICTURE OPERATION

STAGE ELECTRICS AND

ILLUSIONS

CHAPTER I.

THE ELECTRICAL CIRCUIT AND ELECTRICAL HAZARDS.

_Two and Three-Wire Systems._--If the theater electrician will take the

trouble to trace the circuits in the building to their supply, he will

find them entering the building either as two-wire or three-wire

circuits.

[Illustration: FIGURE 1.]

A two-wire circuit is diagrammatically shown in Figure 1. The circuit,

coming from _1_, enters the building, passes through the fuses _2_, and

through switch 3 to the lights. A two-wire system will ordinarily be

found operating at 110 volts, the current varying according to the

number of lights turned on. In the drawing, for instance, only one light

is shown with the switch closed, the other three switches being open.

The current in the circuit is equal to that which passes through the

single lamp. If another switch be closed, another light will burn and

the current will be increased, so that the more lights be turned on, the

greater will be the current.

[Illustration: FIGURE 2.]

The three-wire system, Figure 2, is almost universally used where the

supply is from the outside and where any considerable number of lights

are connected. The chief advantage of the three-wire system lies in its

economy of copper. The middle or neutral wire ordinarily does not carry

current, but it is a necessity whenever the number of lights burning on

the two sides of the system are not equal.

With the neutral wire omitted, we have a straight two-wire system using

double the voltage of the ordinary two-wire system and always operating

two 110-volt lamps in series. Two lamps would always have to be turned

on at the same time and if one of them should burn out, the other would

be extinguished also.

A system using double voltage requires only half the current and

consequently but half the copper. In order to obviate the necessity of

always using two lamps together and at the same time economizing in

copper, the neutral wire is provided. As long as the same number of

lamps are burning on each side of the neutral wire, the same current

always passes through two lamps in series and there is no current in

the neutral. Should, however, the group on one side be turned out, the

other would still continue to burn; but the path of the current to the

dynamo, or bank of transformers, would be through the neutral wire.

The system is thus seen to possess all the advantages of the ordinary

two-wire system since each lamp can be operated by itself and at the low

voltage, while the actual supply voltage for the whole system is double

that which is actually used at any lamp. We have thus two voltages at

our command; 110 and 220 being the voltages in common use.

_Electrical Hazards._--Since this work is not intended for mere

beginners, we shall not enter into elementary considerations, but shall

take up the matter of fire and life hazard, both of which are important

items to which attention cannot be too often called.

The electrical current may cause fire by overheating the wires. This

overheating may be due to the willful overloading of circuits; and to

prevent this, no wire should ever be used to carry more current than is

allowed by the table of carrying capacities given on page 238.

The overheating may also be due to an unknown load which is caused by a

“ground” or a partial short circuit. “Ground” is the technical term used

to designate the connection of a wire to any substance over which

electricity may be carried to the wire of opposite polarity. A ground

may be caused by a bare wire coming in contact with the iron framework

of a building, wet wood, or moist substances of any kind. One such

ground on a circuit can do no harm; but, if one ground exists, in the

course of time another one may come on and, when the second one

appears, if it is on the side of the circuit opposite to the first,

there will be trouble at once.

If the two grounds are both “good”--that is, if they are of low

resistance--we shall have a short circuit and probably blow a fuse; but

if they are not “good,” we may have but a small current which may

continue unnoticed for months. Such a current may eat away the copper of

the positive pole and in time cause the wire to break, creating an

electric arc and perhaps causing a fire. It may also cause wet wood

through which it flows to become charred and finally ignited.

The ground is the bane of the electrical worker. If a system can be kept

free of grounds, the chances of trouble are vastly reduced. The cause of

most grounds is moisture. Nearly all substances except metals are fairly

good insulators if dry; and nearly all of them are fairly good

conductors if sufficiently wet.

Another very prolific source of fires is the electrical spark, large and

small. The spark, due to the breaking of an incandescent lamp, often

causes fires when it comes in contact with inflammable material or

gases. The ordinary lamp cord also causes many fires because it is

easily damaged and liable to short circuits which often result in

arcing. Short circuiting two wires or breaking a wire carrying current

may easily ignite inflammable material in the vicinity.

The best way to reduce the fire hazard to a minimum, is to install all

electrical work carefully according to the rules laid down in the

“National Electrical Code”.

The life hazard is one which concerns the operator personally and is

especially great to those traveling with shows. Traveling men are often

obliged to get along with all sorts of make shifts, especially in the

smaller towns where one-night stands are the rule. Here it is often

necessary to connect to trolley circuits or power lines of different

voltages, frequencies, etc.

A person may suffer injury directly from a current of electricity by

making himself part of the circuit. If the system on which he is working

is alive and grounded, he may easily cause injury to himself by touching

a live wire with his hands while standing upon anything that is

grounded. By so doing he completes a path for the current through his

body.

He may also become part of a circuit by holding a wire with both hands

while someone is cutting it between his two hands. As long as a wire so

held is intact, no shock can be received except to ground, but when the

wire is cut or breaks, a very high voltage may be produced for an

instant which will cause a current through the body of the man holding

the wire. The extra high voltage is produced only if the wire is

carrying current at the time it is being cut. Under these circumstances

there will often be a strong flash, due to the momentary increase in

voltage, produced by the breaking of the circuit, which may be

excessive, especially if there is considerable inductance in the

circuit.

The most frequent cause of injury is due to making contact with the two

opposite polarities of a system. As a rule circuits, with which

operators ordinarily have to work, are low voltage, i.e., not over 220

volts. But many deaths have been caused by this voltage, sometimes

directly and at other times indirectly as, for instance, by causing a

fall. People whose hearts are in any way defective should be careful

about exposing themselves to shocks even at 110 volts.

It is true that many wiremen are in the habit of testing 220-volt

circuits by allowing the current to pass through their bodies, but it

will be noticed that they are very careful not to make a good contact.

The current which passes through the body, when one touches two wires of

opposite polarity very lightly with the finger tips, is but a fraction

of what one would receive if he were unwittingly to grab two wires of

opposite polarities with the hands, especially if the hands were moist.

Numerous cases are on record of persons having been killed by 110 volts

under favorable circumstances; as, for instance, while in the bath

receiving a shock from a so-called vibrator. The body partly immersed in

water and perhaps a foot resting against a water pipe forms a conductor

of very low resistance, and a comparatively strong current may pass

through the body.

The most important precautions against injury while working on live

circuits are:

(1) Insulate yourself from the ground.

(2) Handle only one side of a line at a time.

(3) If possible, work with only one hand at a time in contact with the

wires.

(4) Use rubber gloves, or rubber boots where necessary, but bear in mind

that they are of little value unless kept dry. Moisture will allow some

current to pass over the surface of any substance no matter how good an

insulator it may otherwise be.

(5) Always place yourself so that a slight shock which might cause you

to lose your balance will not give you a bad fall.

(6) Remember that if once you make good contact with an

alternating-current circuit, you cannot let go.

(7) Fix firmly in your mind the directions for resuscitation from

electric shock, on pages 15-18.

When energy is obtained through transformers, there is another danger to

be added to the above, viz., the possibility of the breaking down of the

insulation between primary and secondary wires of the transformer. If

this happens, we have suddenly and without warning, instead of the 110

or 220 volts supposed to exist between the wires forming the circuit,

2,000 or 3,000 volts. Such accidents are especially likely during

thunder storms when lightning often breaks down transformers.

In order to reduce this danger to a minimum, the secondaries of

transformers are grounded. It will be well for the electrician to assure

himself that the secondaries of the transformers from which he is

getting his supply are grounded. This can be tested by an incandescent

lamp. Connect the lamp to ground with one wire and, with the other, try

the two sides of the circuit. If the transformer secondaries are

properly grounded, the lamp will burn at full candle power from one of

the wires; this will show that the other wire is grounded.

A person working on such a circuit is of course more likely to receive a

low voltage shock than if the secondaries were not grounded, but he is

fairly well protected against the primary voltage or lightning.

RESUSCITATION FROM ELECTRIC SHOCK.

Rules recommended by commission on resuscitation from electric shock,

representing The American Medical Association, The National Electric

Light Association, The American Institute of Electrical Engineers: Dr.

W. B. Cannon, chairman; professor of physiology, Harvard University. Dr.

Yandell Henderson, professor of physiology, Yale University; Dr. S. J.

Meltzer, head of department of physiology and pharmacology, Rockefeller

Institute for Medical Research; Dr. Edw. Anthony Spitzka, director and

professor of general anatomy, Daniel Baugh Institute of Anatomy,

Jefferson Medical College; Dr. George W. Crile, professor of surgery,

Western Reserve University; W. C. L. Eglin, past-president National

Electric Light Association; Dr. A. E. Kennelly, professor of electrical

engineering, Harvard University; Dr. Elihu Thomson, electrician, General

Electric Company; W. D. Weaver, secretary, editor Electrical World.

Issued and copyrighted by National Electric Light Association. Reprinted

by permission. Follow these instructions even if victim appears dead.

I. IMMEDIATELY BREAK THE CIRCUIT.

With a single quick motion, free the victim from the current. Use any

_dry non-conductor_ (clothing, rope, board) to move either the victim or

the wire. Beware of using metal or any moist material. While freeing the

victim from the live conductor have every effort also made to shut off

the current quickly.

II. INSTANTLY ATTEND TO THE VICTIM’S BREATHING.

1. As soon as the victim is clear of the conductor, rapidly feel with

your finger in his mouth and throat and remove any foreign body

(tobacco, false teeth, etc.) Then _begin artificial respiration at

once_. Do not stop to loosen the victim’s clothing now; _every moment of

delay is serious_. Proceed as follows:

_a._ Lay the subject on his belly, with arms extended as straightforward

as possible and with face to one side, so that nose and mouth are free

for breathing, see Figure on page 17. Let an assistant draw forward the

subject’s tongue.

[Illustration: INSPIRATION--PRESSURE OFF.]

_b._ Kneel straddling the subject’s thighs and facing his head; rest the

palms of your hands on the loins (on the muscles of the small of the

back), with fingers spread over the lowest ribs, as in Figure on page

17.

_c._ With arms held straight, swing forward slowly so that the weight of

your body is gradually, but _not violently_, brought to bear upon the

subject, see Figure on page 18. This act should take from two to three

seconds.

Immediately swing backward so as to remove the pressure, thus returning

to the position shown in the Figure on page 17.

_d._ Repeat deliberately twelve to fifteen times a minute the swinging

forward and back--a complete respiration in four or five seconds.

_e._ As soon as this artificial respiration has been started, and while

it is being continued, an assistant should loosen any tight clothing

about the subject’s neck, chest or waist.

[Illustration: EXPIRATION--PRESSURE ON.]

2. Continue the artificial respiration (if necessary, at least an hour),

_without interruption_, until natural breathing is restored, or until a

physician arrives. If natural breathing stops after being restored, use

artificial respiration again.

3. _Do not give any liquid by mouth until the subject is fully

conscious._

4. Give the subject fresh air, but keep him warm.

III. SEND FOR NEAREST DOCTOR AS SOON AS ACCIDENT IS DISCOVERED.

Motion Picture Operation, Stage Electrics and Illusions A Practical Hand-book and Guide for Theater Electricians, Motion Picture Operators and Managers of Theaters and Productions · 第 1 / 22 章