BOILER ROOM

=56. Locating the Boiler Room.=—The ideal location for the boilers of

a factory or an industrial plant is in a separate building, which may

be denominated as the =power house=, and which may include as well, the

installation of the engines, dynamos, and other machinery necessary for

the generation of power and its transmission. More frequently, however,

the ground is not available for the erection of a separate building for

the power plant, and it becomes necessary to install the boilers and

engines in the factory itself. The location usually selected for these

vital features of the mill is the basement, and the arrangement of the

boilers and engines must be carefully considered in the designing of

this portion of the building.

=57.= In laying off the space to be occupied by the boilers, the

probable growth of the manufactory must be provided for by arranging

ample space for the installation of additional boilers.

It is best in arranging the boilers, to face them toward the available

coal supply, which is usually a coal bunker, vault, or bin, but in no

instance must the front of the boiler be nearer to a wall than the

length of the boiler tubes, unless special arrangements are made, for

this distance must be allowed in order to draw any defective or damaged

tubes and replace them with new ones. Also, by arranging the boilers

thus, the fireman has a minimum amount of carriage for the coal.

=58. Coal Storage.=—In designing the coal vaults, or coal storage,

their contents should be figured to allow for 1 or 2 weeks’ coal

supply, and as much more as is possible, to carry the plant over

periods of existing coal shortage due to strikes or interrupted traffic

from bad weather or other cause. In calculating the amount of space

required for coal storage, it is sufficient to multiply the number of

horsepower generated by the boilers by 4, which is the approximate

number of pounds of coal per hour for the generation of 1 horsepower.

This result, again multiplied by the number of hours for which the

boilers are run at their capacity, will give the quantity of coal

needed per day, in pounds. The weight per cubic foot of coal varies

from 80 pounds for soft coal to 90 pounds for hard coal, so that by

dividing the number of pounds by these quantities the cubic feet of

coal required per day is obtained. The bins may then be proportioned

for the number of days’ supply which the judgment of the designer may

assume as being necessary.

=59. Ash Disposal.=—Besides the consideration of the coal supply, some

disposition must be made of the ashes from the boilers. Frequently, a

bin is constructed of masonry, alongside of the coal supply, into which

the ashes are dumped by means of barrows. In large plants, this bin can

be emptied by means of an ash conveyor, or elevator, which will carry

the ashes to the level of the street or railroad track and thence into

a cart or car.

=60. Planning the Boiler Room.=—In locating the boilers in the boiler

room, which should be done in the plans of the building, for it is not

customary to cement the floor space covered by the boilers, and the

cost of the building is thus reduced, a passageway not under 3 feet,

and better 4 feet, should be left back of the boilers. This passageway

is required in order to have access to the clean-out doors and the

blow-off cocks. The ordinary horizontal return-tubular boiler, and

some water-tube boilers, can be constructed in a battery, with as many

boilers as may be desired in a row, especially when the passageway

is left back of the boilers. When setting other types of water-tube

boilers, space should be left between each battery of two, for in

these boilers, cast-iron doors are provided in the side walls for

blowing the soot from the tubes, and access must be had through the

side walls of the boiler for this purpose. It is therefore necessary in

laying out the boiler space for boilers of this character to provide

a passageway on one side of each boiler. In Fig. 29, a battery of

return-tubular boilers is indicated, showing the clean-out doors for

taking away the accumulation of soot and ashes that might be back of

the bridge wall, through a passageway at the rear of the boilers. Some

water-tube boilers are set in batteries of two, as the Babcock & Wilcox

water-tube, land-type boiler, which is provided with the necessary

clean-out doors, and doors for blowing the soot off the tubes in the

side wall.

[Illustration: _Front of Boilers_ FIG. 29]

It is therefore necessary in laying out the boiler room of a

manufacturing plant to consider carefully the character of the steam

generator and study its requirements, so that it may be successfully

operated and the proper spaces allotted.

[Illustration: FIG. 30]

=61. Doorway to Engine and Boiler Room.=—In the hasty design of

buildings, it is frequently found that the size of the doorways is not

sufficient to admit the boilers and machinery. This is a serious defect

in the planning of a manufacturing plant, as it requires either the

installation of the boilers and engines before the walls are entirely

built, or else the tearing out of brickwork and jambs in order to

accommodate them afterwards. An expedient for the enlargement of the

headroom of doorways and openings into the boiler and engine rooms that

are in the basement, is shown in Fig. 30. Here, if the lintel of the

doorway _a_ is kept below the floor level, where it would ordinarily

exist, the headroom of the doorway will be materially reduced, and

considerable difficulty will be encountered in taking any large piece

of machinery, or a boiler or steam drum, down the steps _b_. The

doorway is consequently increased in height by the introduction of the

bulkhead at _c_; while by this means the floor space above is slightly

reduced, yet use can frequently be found for the ledge or platform

frame at the top of the bulkhead, as at _d_.

=62. Floors Above Boilers.=—It is important in designing boiler rooms

in factories to have the floor construction over the top of the boiler

of incombustible material, and it is customary in the better class

of buildings to provide a section of fireproof floor over the top

of the boiler room. This floor construction may either be a brick

arch supported on steel beams, or hollow-tile construction, though

reinforced concrete is now finding favor in this purpose.

=63.= It is not altogether necessary that the boilers in a building

shall be placed in the basement, though as this is usually the least

valuable of the floor space it is the practice to so locate them. In

some electric-light stations, and in large factories, boilers have been

located on the first floor, and even in several instances on the fifth

and sixth floors. The exigencies that demand the latter installation,

however, must be great, for it can be readily seen that much power must

be expended in lifting the coal, etc. to the boiler room.