FIG. 19]

=41. Column Footings.=—With factory buildings of more than five or

six stories in height, great pressure is transmitted to the soil from

the base of the bottom column, and as it is necessary with soils of

even fairly good bearing capacity to have footings beneath the piers

supporting columns of from 6 to 10 feet square, adequate means of

providing these footings must be obtained. In Fig. 19 (_a_) and (_b_)

are shown two types of footings for concrete columns. In (_a_) is

indicated a reinforced-concrete column with a steel core. In such an

instance, all the load is transmitted by the steel core through its

angle plates and webbing at the foot to grillage beams. These grillage

beams are, however, not made sufficiently large to transmit the load to

the soil, but merely to distribute the load on the bed of concrete. The

spread portion of the footing is reinforced with steel rods _a_, _a_

crossed each way, and longitudinal shear is taken up in the footing by

means of stirrups _b b_. This is the usual type of footing construction

under reinforced-concrete factory columns.

Where, however, the column is not reinforced with a steel core, but

is merely a pier, footings may be designed as illustrated in Fig. 19

(_b_). Here the base of the column is enlarged in order to better

distribute the load on the several steps of the footing, and where the

bottom step has a considerable overhang, it is reinforced with steel

rods and stirrups, as indicated.

=42. Detail of Slab and Girder Reinforcement.=—In the previous article,

the general construction of the floors and column supports of a factory

building was explained. By referring to Fig. 20, it will be shown how

the girders and beams are reinforced with the steel bars. In this

figure, a plan is indicated at (_a_) and an elevation at (_b_). The rod

reinforcement of the slab is shown in the plan at _a_, _a_. It will be

noticed that over every other beam these rod reinforcements lap, or

break joints, and that some additional tie or reinforcement is placed

over the girders, as indicated by _b_, _b_. These latter rods tend to

tie in the floor slabs still more rigidly than can be accomplished with

their individual reinforcement.

Referring to the elevation (_b_), it will be noticed that all the

reinforcement of the beams is not usually carried along the lower

portion of the girder for its entire distance, but that some of the

reinforcement is bent up at a point about one-quarter of the span

from the abutment, in the form of a camber rod. By arranging the

reinforcing rods in this manner, an additional stirrup action, or tie,

to the girder supports is provided, and the oblique section made by a

horizontal line passing through these rods tends to provide additional

resistance to the horizontal shear in the beams and also provide for

negative bending moment produced in the beams near the support. To

further provide for this, shear stirrups are placed closer together,

toward the abutments, as indicated at _c_, _c_. These stirrups are

ordinarily light pieces of bar iron bent in a =U=-shape, and sometimes

bent around the rod reinforcement, a detail of this stirrup being shown

in Fig. 20 (_c_).

[Illustration: FIG. 20]

Hardware, estimating, and mill design · 第 181 / 194 题