CLASSIFICATION OF FACTORY BUILDINGS

=2.= Classified according to their construction, factory buildings may

be divided into three types, which, for convenience, may be designated

as _first-_, _second-_, and _third-class buildings_. A similar division

to this is also frequently made by the state or municipal laws for the

regulation of the construction of factory buildings.

=3. First-Class Buildings.=—Buildings of the first class are those in

which the walls, floors, columns, girders, beams, partitions, and roofs

are of stone, brick, terra cotta, concrete, steel, iron, and such other

fireproof materials as have been proven to be efficient. Buildings of

this class may be considered as constituting an entirely fireproof

building, which means that while the contents of the building may burn,

the building itself will remain intact, unless subjected to the severe

action of a prolonged conflagration.

=4. Second-Class Buildings.=—Buildings of the second class are

considered to include what is known as slow-burning, or the typical

factory-construction, type, in which all posts or girders must be

of heavy and massive timber, and the floor construction at least

3 inches in thickness, and of solid planking. In buildings of the

second class, while it is permissible to use combustible materials,

they must be of such sizes and of such slow combustion that the

security of the building will be insured for a reasonable time after

the conflagration has commenced. It is usual, therefore, in this

class of building, to limit the size of the wooden posts to not less

than 8 inches square, though their strength may be greatly in excess

of the load they are required to support, and girders and beams are

used whose least dimension is 6 inches or more. In buildings of this

character, it is frequently necessary to use steel beams and columns in

order to obtain the strength for the great floor loads to which these

members are liable to be subjected. When such steel or iron columns

are used, however, they must be fireproofed, because even though made

of incombustible material, they would not have the same endurance in

a fire as have heavy wooden girders or posts, and their failure would

precipitate the fall of the floor. Wooden girders and posts, even

when charred part way through, have still sufficient strength for the

support of the load for which they were designed.

=5. Third-Class Buildings.=—Buildings of the third class are not

particularly recommended for the construction of factory buildings, for

the floors of these may be of the ordinary joist and finished floor

construction. Such buildings are readily ignitible and burn rapidly,

not only because the timber work in them is light, but because of the

numerous air spaces that exist between joists and in the furring of the

walls. No building with air space surrounded by combustible materials

can be considered as slow burning.

Hardware, estimating, and mill design · 第 169 / 194 题