NATIONAL STANDARD PUMP SIZES.(continuation)

======================+===============+================

| [B] Boiler |

Pump Sizes. | Power | Full Speed.

| Required |

------+-------+-------+------+--------+-------+--------

Steam.| Water.|Stroke.|Horse | Steam | Rev. |Piston

| | |Power.| Pres. | Per |Travel

| | | |at Pump,|Minute.|Feet Per

| | | | lbs. | |Minute.

------+-------+-------+------+--------+-------+--------

14 × 7 × 12 | 100 | 40 | 70 | 140

14 × 7-1/4 × 12 | | | |

----------------------+------+--------+-------+--------

16 × 9 × 12 | 115 | 45 | 70 | 140

----------------------+------+--------+-------+--------

18 × 20 × 12 | 150 | 45 | 70 | 140

18-1/2 × 10-1/4 × 12 | | | |

----------------------+------+--------+-------+--------

20 × 12 × 16 | 200 | 50 | 60 | 160

| | | |

----------------------+------+--------+-------+--------

[Footnote B:

This boiler power is required for continuous running at full speed

and pressure. It is, however, often best to put in a larger pump than

the existing boilers could drive at full capacity, as a _small boiler

will drive a 750-gallon pump at the 500-gallon speed with very nearly

as good economy as it can drive a 500-gallon pump at full speed_. The

pump then does not have to be changed when the plant is enlarged and

the boiler power increased.

A steam piston relatively larger than necessary is a source of

weakness. It takes more volume of steam, and gives more power with

which to burst the pipes if the throttle is opened wide suddenly

during excitement.

It has been common to make all fire-pumps with water plunger of

only one-fourth the area of steam piston, with the idea that pump

could thereby be more readily run at night, when steam was low. The

capacity in gallons is thus reduced 25 per cent. as compared with a 3

to 1 plunger on the same steam cylinders.]

_b._ The above sizes of steam and water cylinders and length of stroke

have given general satisfaction and will now be considered as standard.

Often, especially with large pumps, “4 to 1” construction is a

mistake, and gives no additional security, although the pump might

start and give a few puffs with 30 lbs. of steam on banked fires;

because, if any pump of whatever cylinder ratio draws 50 or 100

horse-power of steam from boilers with dead fires, it can run

effectively only a very short time (ordinarily, perhaps, 3 to 5

minutes), unless fires are first aroused to make fresh steam to

replace that withdrawn.

Steam pressures stated above must be maintained _at the pump_, to

give full speed and 100 lbs. water pressure. Pressure at boilers must

be a little more, to allow for loss of steam pressure between boiler

and pump. Pumps in poor order, or too tightly packed, will require

more steam.

The boiler horse-powers above are reckoned on the A. S. M. E. basis

of 34-1/2 lbs. of water evaporated from and at 212 degrees Fahrenheit

as the unit of boiler horse-power. From 12 to 15 square feet of

water-heating surface in the boiler is commonly assumed necessary for

the generation of one horse-power.

Smaller boilers than called for above, if favorably set, and having

excellent chimney draft, can sometimes be forced to nearly double

their nominal capacity for a short run, as for fire service.

_c._ _250 gallons per minute is the standard allowance for a good

1-1/8-inch (smooth nozzle) fire stream._

A so-called “Ring Nozzle” discharges only three-fourths as much water

as a smooth nozzle of the same bore, and is not recommended.

From fifteen to twenty automatic sprinklers may be reckoned as

discharging about the same quantity as a 1-1/8-inch hose stream under

the ordinary practical conditions as to pipes supplying sprinkler and

hose systems respectively.